摘要
功率因数校正是产生或吸收无功功率力图达到功率因数等于1。单级交-交变流器被广泛应用在各工业领域。传统的交-交变流器采用电压调制法,全谐畸变高,功率因数低,功率转换效率差。本文介绍全新直流调制方法,由直流变流技术实现。直流调制单级功率因数校正交-交变流器有效地改进了功率因数,使之达到0.999,功率转换效率达到97.8%。实验结果证实了设计和计算的正确性。
Power factor correction (PFC) is the capacity of generating or absorbing the reactive power produced by a load for possible unity power factor. Single-stage AC/AC converters are the most popular structure widely applied in various industrial applications. These AC/AC converters are traditionally implemented by voltage regulation technique. However, they have high total harmonic distortion (THD), low power factor (PF) and poor power transfer efficiency (η). In this paper, a novel approach method named DC-modulation that implements DC/DC conversion technology into the AC/AC converters is introduced. The DC-modulated single-stage power factor correction AC/AC converters effectively improve the power factor up to 0.999 and the power transfer efficiency up to 97.8%. The experimental results verify our design and calculation. This technique will be widely applied in many industrial applications.
出处
《电工技术学报》
EI
CSCD
北大核心
2007年第5期92-103,共12页
Transactions of China Electrotechnical Society
关键词
直流调制
功率因数校正
电压调制法
交-交变流器
全谐崎变
功率转换效率
数学模型
DC-modulation, power factor correction, voltage regulation technique, DC-modulated AC/AC converters, total harmonic distortion, power transfer efficiency, mathematical modeling