期刊文献+

500kV电容式电压互感器电容值及介损值的现场测试 被引量:9

Filed Measurement of Capacity and Dielectric Loss on Site for the TEHMP-500 Type 500kV Capacitive Voltage Transformer
下载PDF
导出
摘要 TEHMP-500型500kV电容式电压互感器(CVT)由于在中间变压器一次绕组首端位置设置了一把接地刀闸,在现场测试中,通过操作外部的操作把手合上接地刀闸,使中间变压器一次绕组首端接地,可以很方便地采用反接法测试C13及C2的电容值及介损,克服了采用自激法测试的弊端。 In the TEHMP-500 Type 500kV CTV, a grounding-switch is set in the front of the middle transformer primary turn. During measurement on site, the front of the middle transformer primary turns becomes on grounding through operating the outside handle to close the grounding-switch. Thus the capacitances of C13 and C2 and dielectric loss can be measured conveniently using inverse connecting method , the disadvantages of self-excitation method can be avoided.
作者 赵汝国
出处 《电力电容器》 2007年第3期46-47,共2页 Power Capacitors
关键词 电容式电压互感器(CVT) 中间变压器 接地刀闸 Capacitor Voltage Transformer(CVT) Middle Transformer Grounding-switch
  • 相关文献

参考文献2

  • 1陈化钢.电气设备预防性试验方法[M].北京:水利电力出版社,1999.
  • 2电气设备预防性试验规程(DL/T596-1996).