摘要
给出了无源滤波装置参数设计的计算方法及仿真模型。依据无源滤波装置的基本原理给出了10 kV母线无源滤波装置参数的选择方法,并进行了具体的计算,得出了各元器件具体的参数。提出了在系统参数摄动的情况下对无源滤波装置的滤波效果的监控模型。基于S imu link仿真结果表明,该方法设计的无源滤波装置是可行的。
The paper demonstrated the calculation method of parameter design of passive filter and its simulating model, and brought forward the selecting method of parameter for lOkV busbar passive filter and gained the concrete parameters for all kinds of components based on calculation in details according to the basic mechanism of passive filter. Finally, the model to monitor the filtering effectives of passive filter was put forward under the situation of system parameter vibration, the actual simulating results showed that the passive filter designed with the method is feasible and practical.
出处
《黑龙江电力》
CAS
2007年第3期177-180,共4页
Heilongjiang Electric Power