期刊文献+

河北南网两起高频保护误动作事故分析与对策 被引量:1

Analysis on two Malfunctions of High Frequency Protection in Hebei Southern Power System and Their Countermeasures
下载PDF
导出
摘要 通过河北南网发生两起高频保护误动作事故,分析是由生产厂家制造错误和回路接线错误所致。并提出了对JSF-11C装置的漏制造的印刷条用跨线连接焊好;取消与901微机保护配合的收发讯机的“位置停讯”回路;利用901内部远方启迅逻辑;901保护与SF—600可采用单对接点连接。 Two malfunction failures of High frequency protection occurred in Hebei Southern Power Grid. By analyzing,the causes of the failures were found due to manufacture error in circuit wiring. A missing segment of printed circuit in JSF 110 device was connected with a jumper, Cancel the circuit of “position stop of communication” in the receiver transmitter unit in coordination with 901 microcomputer based protection; Make use of the remote start logic in the 901; The 901 protection and SF 600 can be connected with single pair of contact.
出处 《河北电力技术》 1997年第1期12-17,共6页 Hebei Electric Power
关键词 河北 电网 高频保护 误动事故 High frequency protection circuit connection receiver transmitter unit single pair of contact
  • 相关文献