期刊文献+

加压送风量与门两侧压差值关系的网络模拟分析 被引量:2

Network simulation for relationship of pressurized supply air rate and pressure difference across the door
下载PDF
导出
摘要 利用多区域网络模型,以20层高层建筑为例,分别对各种加压方式下的加压送风量与门两侧压差值的关系进行了定量模拟分析。模拟结果表明,加压送风量的大小对门两侧压差值特别是着火层门两侧的压差值具有决定性的影响。 Taking a twenty storied high-rise building for example, uses a multizone network model to simulate the relationship of the pressurized supply air rate and the pressure difference across the door under various pressurized conditions, providing a quantitative analysis method of evaluating the availability of the smoke control system. The result shows that the pressurized supply air rate has a significant effect on the pressure difference across the door especially the door in the fire floor.
机构地区 哈尔滨工业大学
出处 《暖通空调》 北大核心 2007年第8期79-83,110,共6页 Heating Ventilating & Air Conditioning
关键词 多区域网络模型 加压方式 加压送风量 压差值 multizone network model, pressurized method, pressurized supply air rate, pressure difference
  • 相关文献

参考文献6

  • 1中华人民共和国公安部.GB 50045-95 高层民用建筑设计防火规范(2005版)[S].北京:中国计划出版社,2005
  • 2Musser A M.Multizone modeling as an indoor air quality design tool[C]// Healthy Buildings 2000,6th International Conference Proceedings.Finland,2000(2):455-460
  • 3Dols W S.A tool for modeling airflow and contaminant transport[J].ASHRAE Journal,2001,43(3):35-42
  • 4Walton G N.CONTAMW2.4 user manual[M].NISTIR 7251.National Institute of Standards and Technology,Gaithersburg,MD,2004
  • 5Persily A K,Elizabeth M I.Input data for multizone airflow and IAQ analysis[R].National Institute of Standards and Technology.NISTIR 6585,Gaithersburg,MD,2001
  • 6高甫生,王砚玲,邱旭东.高层建筑加压送风系统试验研究[J].暖通空调,2003,33(4):31-35. 被引量:10

二级参考文献1

  • 1.GB 50045—95.高层民用建筑设计防火规范[S].,1995..