期刊文献+

闭式水系统中补水泵的设置

Setup of make-up water pumps for closed water systems
下载PDF
导出
摘要 结合相关规范的规定,提出了暖通空调闭式水系统正常补水泵和事故补水泵应分开设置。正常补水泵用于水系统正常运行时的补水,流量宜为系统水容量的1%或者供热系统循环流量的2%,并进行变频调速控制;事故补水泵台数不宜过多也不宜少于2台;事故补水泵和正常补水泵均可不设备用泵。 With the provisions in relating codes, states that normal make-up water pumps and accident make-up water pumps should be set separately for a closed HVAC water system. Normal make-up water pumps provide make-up water in normal operation with the water flow rate of one percent of system water volume or of two percent of circulating water quantity of a heating system, applying variable frequency control at the same time. There should not be too many accident make-up water pumps in a system, but the number of the pump should not be less than two. It is unnecessary to install spare pumps for normal and accident make-up water pumps.
出处 《暖通空调》 北大核心 2007年第8期128-129,160,共3页 Heating Ventilating & Air Conditioning
关键词 补水泵 变频 节能 闭式水系统 make-up water pump, variable frequency, energy saving, closed water system
  • 相关文献

参考文献9

二级参考文献10

  • 1机械工业部.机械设计手册 第12分册 通用设备.第2版.北京:机械工业出版社,1997
  • 2谷津和久 梶山浩行 成瀬彰彦.送水壓力制御装置[P].日本專利,3122978.2000-1027.
  • 3ASHARE. ASHARE Handbook (HVAC Applications,HVAC Systems and Equipment, Fundamentals,Refrigeration). 1999- 2002
  • 4空気調和·衛生工学会.空気調和·衡生工学便覧,第13版[M].,2002..
  • 5施俊良.室温自动调节原理和应用.北京:中国建筑工业出版社,1983
  • 6廖传善,叶振猷,卢紫珊.空调设备与系统节能控制.北京:中国建筑工业出版社,1984
  • 7Bernier M A, Bourret 13. Pump energy and variable frequency drives. ASHRAE J, 1999, 41(12) :37- 40.
  • 8张燕宾.SPWM变频调速应用技术[M].北京:机械工业出版社,2001..
  • 9李锡冲.空调两级泵水系统变频调速的自控设计[J].暖通空调,2001,31(6):51-54. 被引量:8
  • 10陈焰华,武笃福.冷水机组水系统的配置及设计[J].暖通空调,2003,33(6):67-69. 被引量:8