超导故障限流器对电力系统暂态稳定性的影响分析 被引量:10

Influence Analysis of Transient Stability for Superconducting Fault Current Limiter on Power System
下载PDF
导出
摘要 根据超导故障限流器(SFCL)失超后表现出的阻抗特性,可将SFCL分为2类:电感型和电阻型。针对单机无穷大系统,推导出了在输电线路不同位置发生短路故障时,投入超导故障限流器后的总转移阻抗和发电机的输出功率表达式。从功角特性曲线上分别分析了电感型和电阻型超导故障限流器对电力系统暂态稳定性的影响情况,从数学上进行了证明,并从物理上进行了解释。最后用改进欧拉法编程,对接入SFCL的电力系统进行了暂态稳定时域仿真研究。 According to the characteristics of superconducting fault current limiters ( SFCL ), the SFCL can be divided into two types: inductor type and resistor type. The total transfer impedance and the generator power-output expressions are deduced after introducing SFCL when short circuit faults occurs on different locations of a transmission line in a single machine to infinite-busbar system. From the view of the power angle relationship, the effects of inductor type and resistor type SFCL on power system transient stability are analyzed, a mathematical proof and a physical explanation are also given. The improved Euler algorithm is used for the time-domain simulation of transient stability to proving the analytical results.
出处 《湖南工业大学学报》 2007年第4期22-28,共7页 Journal of Hunan University of Technology
关键词 超导故障限流器 电感型 电阻型 暂态稳定 superconducting fault current limiter inductor type resistor type transient stability
  • 相关文献

参考文献10

二级参考文献29

  • 1韩朔 张炳南 等.超导技术应用发展对策报告.国家科委超导技术应用对策研究课题组[M].,1989..
  • 2White.G.K 洪朝生等译.[M].北京:科学出版社,1962..
  • 3[1]Raju B P, Parton K C, Bartram T C, Acurrent limiting device using superconducting DC bias applications and prospects. IEEE Trans on Apparatus and System. 1982,101 (9): 3173- 3177
  • 4[2]Keilin V, Kovalev I, et al. Model of HTS three-phase saturated core fault current limiter. IEEE Trans. on Applied superconductivity, 2000,10(1): 836-839
  • 5[3]Matsumura T, Shimizu H, Yokomizu Y, Design guideline of flux-lock type HTS fault current limiter for power system application. IEEE Trans. on Applied superconductivity, 2001,11 (1): 1956-1959
  • 6[4]Hoshino T, Mutai, Load test on superconducting transformer and fault current limiting devices for electric power system. IEEE Trans. On Magnetics, 1994,30(4):2018-2021
  • 7[5]Shimizu S, Kado H, et al. Single-line-to-ground fault test of a 3-phase superconducting fault current limiting reactor. IEEE Trans. on Magnetics, 1992,28 (1): 442- 445
  • 8[6]Tixador P, Experimental results on an hybrid superconducting current limiter. IEEE Trans. on Applied Superconductivity, 1995,5 (2): 1055- 1058
  • 9[7]Bashkirov Yu A, Yakimets I V, et al. Application of superconducting shields in current-limiting and special- purpose transformers. IEEE Trans. on Applide superconductivity, 1995,5 (2): 1075-1078
  • 10[8]Sokolovsky V, Meerovich V, et al. AC losses in BSCCO cylinders operating in inductive current limiter. IEEE Trans, on Applied Superconductivity, 1999,9(2): 1361- 1364

共引文献158

同被引文献95

引证文献10

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部