期刊文献+

关于制药车间百级灌装区背景环境级别设置的分析 被引量:1

Analysis on background environment cleanliness of class 100 filling zone in pharmaceutical workshops
下载PDF
导出
摘要 从工艺和净化两方面分析了欧盟GMP洁净级别划分中B级的设置,认为B级静态条件下洁净度定为百级是没有必要的,静态条件下洁净度万级就可以满足欧盟GMP和ISO14644中A区沉降菌小于1个/(4h)的要求。建议在修订我国GMP时可向国际标准靠拢,即B区静态级别不定,只定动态万级或为高于万级的某级。 Analyses the class B specified in European GMP from both production requirement and clean technology.Considers that it is not necessary to set class B to meet the cleanliness of class 100 at static status.As long as the controlled clean zone could reach the cleanliness of class 10 000 at static status,the CFU test results could satisfy the requirements of both ISO 14644 SPC and European GMP,i.e.less than one CFU for four hours in class A zone.Proposes referring the international standard in revising China's GMP.And the possible scheme is not to determine the cleanliness at static status in class B zone by just specifying that the operational requirement is the cleanliness of class 10 000 or higher.
出处 《暖通空调》 北大核心 2007年第9期59-64,共6页 Heating Ventilating & Air Conditioning
关键词 GMP A区、B区灌装 制药车间 GMP,class A and class B filling zone,pharmaceutical workshop
  • 相关文献

参考文献1

  • 1许钟麟.空气洁净技术原理[M].北京:科学出版社,2003.

共引文献40

同被引文献2

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部