摘要
某变电所1台大型电力变压器在投入运行后,其绝缘电阻逐年下降。通过对变压器油进行色谱分析,试验各项指标无异常,但油中含有大量微生物。采用高效吸附剂处理变压器油,效果良好。
Its insulated resistance has decreased year by year after a large capacity transformer put into use in a substation. The results of chromatographic analysis of transformer oil showed that all kinds of index are acceptable; however there is lot of microorganism in oil. Using high efficient absorbent to handle the transformer oil is a correct way, which solve that problem.
出处
《黑龙江电力》
CAS
2007年第4期273-274,276,共3页
Heilongjiang Electric Power
关键词
变压器
微生物
绝缘电阻
泄漏电流
色谱分析
transformer
microorganism
insulated resistance
leakage current
chromatogram