基于特高压电网潜供电流的研究 被引量:9

Study on Potential Supply Current Based on UHV Electric Network
下载PDF
导出
摘要 我国超高压线路一般都采用单相重合闸,以提高系统运行的稳定水平,降低单相重合闸的过电压。特高压线路也拟采用单相重合闸,但特高压线路的潜供电流大,恢复电压高,潜供电弧难以熄灭,可能影响单相重合闸的无电流间歇时间和成功率,针对此种情况,在探讨潜供电流产生机理的基础上研究了限制潜供电流和加快潜供电弧熄灭的措施。 In our country,single-phase reclosing is generally adopted in EHV lines to improve the system operation stability and reduce over-voltage of the single-phase reclosing.Single-phase reclosing is planned in UHV lines,but the potential supply current in EHV lines is high,recovery voltage is high,potential arc can hardly be quenched and it is possible to affect no-current intermittent time of the single-phase reclosing and probability of success.For this case,we develop how to limit measures of potential supply current and accelerating potentral arc extinction on the basis of disassing the mechanism by produced by potential current.
出处 《电气开关》 2007年第5期30-32,35,共4页 Electric Switchgear
关键词 重合闸 潜供电弧 reclosing poteutial arc
  • 相关文献

参考文献4

二级参考文献15

  • 1商立群,施围.快速接地开关熄灭同杆双回输电线路潜供电弧的研究[J].电工电能新技术,2005,24(2):5-7. 被引量:17
  • 2蔡汉生,张丽泉.500kV线路并联电抗器过补偿运行时的计算与分析[J].中国电力,1996,29(3):38-42. 被引量:9
  • 3IEEE Committee Report.Single phase tripping and auto reclosing of transmission lines [J].IEEE Trans.on Power Delivery,1992,7(1): 182-192.
  • 4Atmuri S R,Thallam R S,Gerlach D W,et al.Neutral reactors on shunt compensated EHV lines [A].Proc.1994 IEEE Power Eng.Society Transmission and Distribution Conf.[C].Chicago,IL,USA,1994.121-128.
  • 5Y Goda,S Matsuda,T Inaba,et al.Forced extinction characteristics of secondary arc on UHV(1000kV class) transmission lines [J].IEEE Trans.on Power Delivery,1993,8(3): 1322-1330.
  • 6Gary C Thomann,Stephen R Lambert,Somkiet Phaloprakam.Non-optimum compensation schemes for single pole reclosing on EHV double circuit transmission lines [J].IEEE Trans.on Power Delivery,1993,8(2): 651-659.
  • 7HASIBER R M, JEGATE A C, BRUNKER J, et al. The application of high-speed grounding switches for single-pole reclosing oil 500 kVpower system [J]. IEEE Transactions on Power Apparatus and System,1981, 100(4):1512-1515,.
  • 8ESZTERGALYOS J, ANDRICHAK J, COLWELL D H, et al. Single phrase tripping and auto reclosing of transmission lines [J]. IEEE Transaction on Power Delivery, 1992, 7 ( 1 ):182-192.
  • 9GODA Y, MATSUDA S, INABA T, et al. Forced extinction characteristics of secondary arc, on UHV (1 000 kV class) transmission lines[J ].IEEE Transaction on Power Delivery, 1993, 18 (3):1322-1330.
  • 10GODA Y, MATSUDA S, INABA T, et al, Insulation recovery characteristics after fault arc interruption on UHV ( 1 000 kV class) transmission lines [J ]. IEEE Transaction on Power Delivery, 1993, 8 (4):1907-1912.