期刊文献+

先进的高压侧电压控制改善电压稳定性 被引量:4

Advanced high side voltage control improves voltage stability
下载PDF
导出
摘要 基于常规的发电机励磁系统控制方法,通过引入补偿控制的方式,提出了一种改进的先进的高压侧电压控制(AHSVC)方法,并论述了其工作原理、实现方式及特性。现有的AHSVC方法没有计及发电机有功电流的影响,而改进方法根据严格的理论推导,在机端电压的计算中同时计及由发电机无功电流和有功电流引起的压降,并引入下降率电抗,以平衡并列运行发电机之间的电流和无功功率,通过机端电压设定值准确控制高压侧电压的目标设定值。通过数值仿真结果分析,证明了该改进方法的有效性和实用性。由于不需要任何高压侧反馈信号,所以易于实现且经济。 An improved AHSVC(Advanced High Side Voltage Control) is presented,which introduces supplemental control to conventional generator excitation system. Its working principle,characteristics and implementations are described. The existing AHSVC ignores the influence of active current on voltage stability,while the improved control considers the voltage drop caused by both active and reactive currents according to rigorous theoretic deduction in generator terminal voltage calculation and introduces the ramp reactance to balance the current and reactive power among the parallel generators. The high side voltage of a step- up transformer is controlled accurately by the setting of generator terminal voltage. Simulation results prove the effectiveness and practicability of the improved method. It is relatively cheap and easy to be implemented because no feedback signal from the high voltage side is needed.
出处 《电力自动化设备》 EI CSCD 北大核心 2007年第10期43-46,共4页 Electric Power Automation Equipment
关键词 电力系统电压稳定 励磁系统 自动电压调节器 先进的高压侧电压控制 补偿控制 power system voltage stability advanced high side voltage control supplemental excitation system automatic voltage regulator control
  • 相关文献

参考文献14

二级参考文献121

  • 1张步涵,刘小华,万建平,刘沛,程时杰.基于混沌时间序列的负荷预测及其关键问题分析[J].电网技术,2004,28(13):32-35. 被引量:46
  • 2邓集祥.电力系统分歧浅析[J].控制与决策,1993,8(2):111-115. 被引量:4
  • 3刘劲,孙扬声,陈德树.周期参数扰动电力系统中的倍周期分叉、混沌和奇怪吸引子[J].电网技术,1996,20(8):1-3. 被引量:7
  • 4王伟胜,王建全,朱振青,夏道止.应用潮流雅可比矩阵判别小干扰电压稳定性的原理及条件[J].电力系统自动化,1996,20(9):8-11. 被引量:10
  • 5马大强(Ma Daqiang).电力系统机电暂态过程(Power system mechanical-electrical transient course)[M].北京:水利电力出版社(Beijing:Hydraulic and Electric Power Press),1988..
  • 6韩祯祥(Han Zhenxiang).电力系统稳定(Power system stability)[M].北京:中国电力出版社(Beijing:China Electric Power Press),1995..
  • 7Mello F P de, Concordia C. Concepts of synchronous machine stability as affected by excitation control[J].IEEE Trans. PAS, 1969, 88:316-329.
  • 8Hurley J D, Bize L N, Mummelt C R. The adverse effects of excitation system vat and power factor controllers[J]. IEEE Tran. on Energy Conversion, 1999, 14(4): 1636-1645.
  • 9Michigami T, Onizuka N, Kitamura S. Development of advanced generator excitation conlrol regulator (PSVR) for improving voltage stability of a bulk power transmission system: the institute of electrical engineers of japan[J]. 1990, 110-B(11): 887-894.
  • 10Hitomi Kitamura, Masaru Shimomura et al. Improvement of voltage stability by the advanced high voltage control regulator[C]. IEEE Summer meeting-2000.

共引文献115

同被引文献56

引证文献4

二级引证文献33

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部