期刊文献+

Analysis of capacitive voltage rise during off-line partial discharge tests on power transformers 被引量:1

Analysis of capacitive voltage rise during off-line partial discharge tests on power transformers
下载PDF
导出
摘要 Partial discharge test on a transformer is carried out according to the items in IEC 60. During the test, unproved measuring system is calibrated by proved system at a voltage no less than 50% the rated testing voltage. The result is then extrapolated linearly, leading to an error related to the distribution of stray capacitance, which varies with the testing frequency, especially to large transformers. In this paper a factor, named the capacitive rise fact, is introduced to assess the rise. The factor can be adjusted to some extent by changing the reactance that is connected to the LV side of the testing circuit to lower the capacity of the power source. However, the factor changes when the voltage divider on the high voltage side is removed after the voltage ratio has been calculated, and a great error is resulted under unfavorable conditios. Partial discharge test on a transformer is carried out according to the items in IEC 60. During the test, unproved measuring system is calibrated by proved system at a voltage no less than 50% the rated testing voltage. The result is then extrapolated linearly, leading to an error related to the distribution of stray capacitance, which varies with the testing frequency, especially to large transformers. In this paper a factor, named the capacitive rise fact, is introduced to assess the rise. The factor can be adjusted to some extent by changing the reactance that is connected to the LV side of the testing circuit to lower the capacity of the power source. However, the factor changes when the voltage divider on the high voltage side is removed after the voltage ratio has been calculated, and a great error is resulted under unfavorable conditios.
出处 《Journal of Shanghai University(English Edition)》 CAS 2007年第5期490-495,共6页 上海大学学报(英文版)
关键词 TRANSFORMER stray capacitance partial discharge test. transformer, stray capacitance, partial discharge, test.
  • 相关文献

参考文献7

  • 1.Power Transformers—Part 3:Insulation Levels,Dielectric Tests and External Clearances in Air[].IEC Standard -:.2000
  • 2.High-voltage Test Tech- niques—Partial Discharge Measurements IS][].IEC Standard :.2000
  • 3.Insulation Co-ordination—Part 2:Application Guide[].IEC Standard -:.1996
  • 4.High-Voltage Test Tech- niques—Part 1:General Definitions and Test Require- ments[].IEC Standard -:.1989
  • 5VERMEULEN H J,DANN L R.Equivalent circuit mod- eling of a capacitive voltage for power system harmonic frequencies[].IEEE Transactions on Power Delivery.1995
  • 6BLACHE F,KERADEC J P.Stray capacitances of two winding transformers:equivalent circuit,measure- ments,calculation and lowering[].Proceedings of Con- ference Record of the IEEE Industry Application Society Annual Meeting.1994
  • 7SAMESIMA M I,DE OLIVEIRA J C,DIAS E M.Fre- quency response analysis and modeling of measurement transformers under distorted current and voltage sup- ply[].IEEE Transactions on Power Delivery.1991