期刊文献+

系统电压不对称条件下ASVG的仿真分析 被引量:15

Influence of voltage unbalance on the advanced static var generator
原文传递
导出
摘要 从理论分析和仿真两个方面,对先进静止无功功率发生器(ASVG)在系统电压不对称条件下的运行特性进行了详细的分析,指出了由于负序电压造成的功率流动所引起直流电容电压脉动和负序电流的影响,是决定ASVG运行性能的关键因素。不对称度的增加将进一步增大电容电压的脉动和负序电流的大小。采用系统电压正序分量作为逆变电压的同步信号,增大电容量C和漏抗值L的大小,在直流电容侧并联100Hz的LC谐振滤波器等措施。 ? The influence of the system voltage unbalance on the advanced static var generator (ASVG) has been discussed through the ways of theoretical analysis and simulation. It is recognized that the DC capacitor voltage pulsation and negative sequence current, which is caused by the power flow due to the system negative sequence voltage, is the key point that influences the operation of ASVG. Larger system voltage unbalance degree causes larger capacitor voltage pulsation and negative sequence current. Using the following control method such as choosing the positive sequence voltage as the synchronizing signal of ASVG output voltage, using larger capacitor C and reactance L, and using a 100 Hz LC resonant filter, restrain the influence of the system voltage unbalance effectively. 
出处 《清华大学学报(自然科学版)》 EI CAS CSCD 北大核心 1997年第7期55-58,共4页 Journal of Tsinghua University(Science and Technology)
关键词 无功补偿 仿真 电力系统 静止无功发生器 reactive power compensation unbalance negative sequence simulation
  • 相关文献

同被引文献153

引证文献15

二级引证文献134

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部