摘要
利用生物接触氧化工艺和调整鼓风量改造原处理工艺,处理购物中心综合污水,设计能力400m3/d。废水进水水质CODCr为1083~1146mg/L、SS为315~436mg/L;调试稳定后,出水水质CODCr为126~145mg/L、SS为65~83mg/L,CODCr、SS去除率分别为87%~93%、79%~81%,出水水质达到国家二级排放标准。
Biological contact oxidation process and regulation of aircapacity were used to modify the former process so as to dispose shopping center comprehensive wastewater.Whose design capacity was 400 m^3/d .COD_ Cr contained in influent was 1 083 ~ 1 146 mg/L ,SS 315~436 mg/L,after debugging, COD_ Cr in effluent was 126~145 mg/L,SS 65~83 mg/L,the removal rates of COD_ Cr and SS were 87%~93% and 79%~81%.The effluent quality could reach the standard of the national second class discharge.
出处
《环境工程》
CAS
CSCD
北大核心
2007年第5期100-102,共3页
Environmental Engineering
关键词
生物接触氧化工艺
购物中心
综合污水
调试
运行
biological contact oxidation process, shopping center, comprehensive wastewater, debugging and operation