期刊文献+

新型共沸混合工质HC170/FC116沸腾传热实验研究

EXPERIMENTAL STUDY OF POOL BOILING HEAT TRANSFER OF HC170/FC116 SYSTEM
下载PDF
导出
摘要 实验测量了新型共沸混合工质HC170/FC116的池核沸腾传热特性。实验测量的加热面为紫铜表面,热流密度范围为50 kW/m^2~300 kW/m^2.同时实验结果与复叠温区常用制冷剂R503和R508B的传热性能进行了比较,发现新型共沸混合工质HC170/FC116的传热性能高于R508B.最后对实验数据回归得到了共沸混合工质传热系数计算关联式,此关联式的计算值与实验数据的偏差在±10%以内. Nucleate pool boiling heat transfer data on a smooth fiat surface have been systematically measured in HC170/FC116 system. The experiment was carried out at different heat fluxes from 50 to 300 kW/m^2. The experimental results are compared with the measured data of both systems of R503 and R508B. It can be found that HC170/FC116 system showed higher heat transfer coefficient than R508B system. The comparison between all calculated values and experimental data shows a good agreement. The maximal deviation is within 4-10%.
出处 《工程热物理学报》 EI CAS CSCD 北大核心 2007年第6期992-994,共3页 Journal of Engineering Thermophysics
基金 国家自然科学基金项目(No.50576102)
关键词 混合工质 共沸 沸腾传热 传热系数 mixed-refrigerant azeotropic boiling heat transfer heat transfer coefficient
  • 相关文献

参考文献3

  • 1公茂琼,吴剑峰,张宇.一种适用于两级复叠制冷系统中低温的混合制冷剂.中国发明专利,200510123231,2,2005
  • 2Zhang Yu, Gong Maoqiong, Zhu Hongbo, et al. Vapor-Liquid Equilibrium Measurements for the Ethane+Hexafluoroethane System over a Temperature Range from (199.64 to 242.93) K. Chemical Engineering Data, 2005, 50(6): 2074-2076
  • 3B N Taylor, C E Kuyatt. Guidelines for Evaluation and Expressing the Uncertainty of NIST Measurement Results. NIST Technical Note 1297, 1993