期刊文献+

大空间卷烟制丝车间烟气控制性能化设计 被引量:2

A performance-based design on smoke control in a large space primary of cigarette processing workshop
下载PDF
导出
摘要 为分析某大空间卷烟制丝车间(长203.9m,宽72m,高16.7m)防排烟设计效果,对其典型可燃物进行实体火灾实验,得到其热释放速率为41.1~98.0kW/m^2,确定其火灾模型为慢速发展的t^2火.然后用性能化消防设计的方法、运用FDS火灾模拟软件对其进行数值模拟,结果显示在不同火灾场景下火灾发展到2400s时车间2m高度以下烟气温度、CO浓度均能满足人员生命安全的性能指标,而能见度指标在2000s之后低于10m.多台风机同时排烟是导致烟气较快弥漫的主要因素,高大空间工业建筑设计机械排烟系统时宜划分防烟分区,并考虑分时段分区域启动,划分防烟分区的挡烟垂壁高度不宜小于0.7m. A series of real fire tests for typical combustible objects were carried out to investigate the effects of smoke pre- vention and extraction design in a large space primary processing cigarette workshop, 203.9 m long, 72 m wide and 16.7 m high. Fire tests show that the heat release rate in the workshop is 41.1~98. 0 kW/m^2 and develops as a slow t^2 fire. FDS was used to simulate the fire development in the workshop according to the fire performance-based design. Simulation results prove that both the index of smoke temperature and CO concentration below 2 m's high in the workshop is safe for human for2400 seconds in each fire scenario, but the index of visibility is lower than 10 m when fires developed to 2000 seconds. The main reason for the smoke spreading more fast is that more than one fan evacuates the smoke at the same time. It is necessary for mechanical smoke extraction design in a large space building to divide smoke bays and to start fanning in different time segments. The height of smoke screens, separating smoke bays, is greater than 0.7 m.
出处 《西安建筑科技大学学报(自然科学版)》 CSCD 北大核心 2007年第5期621-627,共7页 Journal of Xi'an University of Architecture & Technology(Natural Science Edition)
基金 国家自然科学基金项目(50406026)
关键词 卷烟厂 烟气控制 性能化设计 数值模拟 tobacco factory smoke control performance-based design numerical simulation
  • 相关文献

参考文献10

  • 1程远平,陈亮,张孟君.火灾过程中火源热释放速率模型及其实验测试方法[J].火灾科学,2002,11(2):70-74. 被引量:101
  • 2DINENNO P J.Fuel properties and combustion data[C].// DINENNO P J.SFPE Handbook of Fire Protection Engineering.Third Edition.Quincy,MA,USA:The National Fire Protection Association,2002.
  • 3BEYLER C L.Fire dynamics[C].//DINENNO P J.SFPE Handbook of Fire Protection Engineering.Third Edition.Quincy,MA,USA:The National Fire Protection Association,2002.
  • 4CUSTER R L P,MEACHAM B J.Introduction to performance-based fire safety[M].Boston,MA,USA:Society of Fire Protection Engineers,1997.
  • 5DGJ08-88-2000.民用建筑防排烟技术规程[S].[S].公安部上海消防科学研究所 上海市消防局 上海:上海市,2000.6-16.
  • 6程远平,倪照鹏,陈亮,张孟君.性能化防火设计中火灾增长的分析方法[J].消防科学与技术,2004,23(1):9-14. 被引量:8
  • 7ISO/CD 13388-Fire Safety Engineering.Design Fire Scenarios and Design Fires[DB/CD],May 1997.
  • 8BS DD240-1997,Fire Safety Engineering in Buildings[S].London:BSI Technical Committee,1997.
  • 9PURSER D A..Toxicity assessment of combustion products[C] // DINENNO P J.SFPE Handbook of Fire Protection Engineering.Third Edition.Quincy,MA,USA:The National Fire Protection Association,2002:2-83-2-171.
  • 10GNJ1-82,城镇消防站布局与技术装备配备标准[S].北京:公安部,1982.

二级参考文献15

  • 1FWWittbecker.欧共体建筑材料燃烧性能分级标准学术讲座[Z].中国矿业大学,2002..
  • 2[1]ISO/CD 13388-Fire Safety Engineering. Design Fire Scenar ios and Design Fires [DB/CD]. May 1997.
  • 3[2]Walter W. Jones, Glenn P. Fomey. NIST TN 1431, A Technical Reference for CFAST: An Engineering Tool for Estimating Fire and Smoke Transport [ R]. National Institute of Standards and Technology, Building and Fire Research Labo ratory, Gaithersburg, MD 20899, March 2000:17 ~ 77.
  • 4[3]U. Schneider. Ingenieurmethoden im Baulichen Brandschutz [M]. expert-Verlag, Renningen, 2001:151 ~ 187.
  • 5[4]DIN Deusches Institut fuer Normung e.V. Baulicher Brand schutz im Industriebau [ M ]. Berlin: Kommentar zu DIN 18230. Beuth Verlag GmbH, 1999:301 ~ 336.
  • 6[5]ISO/CD 13393 Fire Safety Engineering. Subsystem 4.Detection, Activation and Suppression [ DB/CD ]. May 1997.
  • 7[6]U. Schneider. Bewertung des Abbrandverhaltens yon Stoffen und Waren[M]. Beitrag in Ingenieurmaessige Verfahren im Brandschutz (5). Koeln: VdS Schadenverhuetung. 1998:1~ 32.
  • 8[7]R. John. Rauch- und Waermeabzug bei Braenden in grossen Raeumen [J]. vfdb-Zeitschrift Forschung, Technik und Man agement im Brandschutz, 1988, 38(1): 21 ~ 25.
  • 9[8]ISO 5660-1. Fire tests Reaction to fire Rate of heat re lease from building products [S], First edition (1993).
  • 10[9]ISO 9705. Fire tests Full-scale room test for surface prod ucts [S], First edition (1993).

共引文献115

同被引文献23

引证文献2

二级引证文献6

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部