摘要 从改变有源电力滤波器(APF)中输出低通滤波器(LPF)滤波电感的结构出发,提出一种新型并联混合有源电力滤波器(SHAPF)拓扑。SHAPF能减小控制器带宽、增加系统的稳定裕度,有效抑制数字控制固有延迟引起的负荷与系统间阻抗谐振。它能与无源滤波器并联运行,降低有源部分容量,从而减小损耗和降低装置成本,为非线性负荷电能质量治理提供了新的解决方案。这种新的拓扑结构既适用于单相系统,又适用于三相系统。主要对单相系统进行了分析,动态模拟实验证实了该拓扑结构的可行性。 A novel topology for Shunt Hybrid Active Power Filter (SHAPF) is proposed through modifying the configuration of low pass fiher imluctor in the link of APF and utility grid.This new topology effectively reduces the bandwidth of the controller,and thus increase the stability margin of the system.It is relatively immune to load source impedance resonance caused by inherent digital control delay.And it can be implemented in combination with passive filters to effectively reduce the power rating of the active part,and thereby to reduce the dissipation and cost.This topology provides a novel solution for power quality problems for nonlinear loads.This topologgy is suitable for both single-phase and three-phase system,but the paper concemes only single-phase APF.The effectiveness of the proposed topology is verified by ex-periments.
机构地区 上海交通大学
出处 《电力电子技术》 CSCD 北大核心 2007年第11期23-25,共3页 Power Electronics
关键词 电力系统 滤波器 谐波 功率因数 校正 power system filter harmonic power factor correction
  • 相关文献

参考文献5

二级参考文献14

  • 1FUJITA H, AKAGI H. The Unified Power Quality Conditioner: The Integration of Series-and Shunt-active Filters.IEEE Trans on Power Electronics, 1998, 13(2): 315-322.
  • 2FUJITA H, AKAGI H. A Hybrid Active Filter for Damping of Harmonic Resonance in Industrial Power Systems. IEEE Trans on Power Electronics, 2000, 15(2): 215-222.
  • 3AKAGI H. New Trends in Active Filters for Power Conditioning. IEEE Trans on Industry Application, 1996,32(6): 1312-1322.
  • 4CAVALLINI A, MONTANARI G C. Compensation Strategies for Shunt Active-filter Control. IEEE Trans on Power Electronics, 1994, 9(6): 587-593.
  • 5CHICHARO J F, WANG Hai-hong. Power System Harmonic Signal Estimation and Retrieval for Active Power Filter Applications. IEEE Trans on Power Electronics, 1994, 9 (6):580-586.
  • 6Akagi H.New Trends in Active Filters for Power Condition[J].IEEE Transactions on Industry Application,1996,32 (6):1312-1322.
  • 7Darwin Rivas,Luis Moran.Improving Passive Filter Compensation Performance with Active Techniques[J].IEEE Trans. on Power Electronics,2003,50(1):161-170.
  • 8Bhattacharya S, Divan D, Cheng P. Hybrid Solutions for Improving Passive Filter Performance in High Power Applications[J].IEEE Trans. on Ind. Applicat.,1997,33: 732-747.
  • 9Akagi H.New Trends in Active Filters for Power Conditioning[J]. IEEE Trans. on Indus. Appl. 1996,32(6):1312-1322.
  • 10李金平,刘善军.地壳形变与地面温度异常及其关联分析:以汶川地震为例[J].地理与地理信息科学,2009,25(1):79-83. 被引量:7