摘要 笔者总结了示范工程中变压器现场局放交接试验的程序、标准、过程,分析了出现的问题,提出如下建议:①提高750 kV变压器的工频试验电压;②不宜反复进行局放试验;③现场试验局放超标时应务实处理;④重新定义局部放电起始电压和熄灭电压;⑤必要时采用可靠的在线监测设备。这些建议不限于750 kV变压器,亦可为1 000 kV变压器的现场交接试验参考。 This paper analyzes the problems concerning pro- cedure, standards, and process in the on-site acceptance partial-discharge(PD) test on the 750 kV transformers. Some suggestions are therefore offered as follows:(1)increase the power frequency withstand test voltage for 750 kV transformers; (2)avoid to perform PD test repeatedly;(3)take practical measures if PD quantity exceeds the criterion stated in standard; (4)redefine the PD inception voltage and extinction voltage; (5)use reliable on-line monitoring apparatus when necessary. These suggestions can also serve as a reference for the same test on 1 000 kV transformer.
出处 《高压电器》 EI CAS CSCD 北大核心 2007年第6期434-437,共4页 High Voltage Apparatus
关键词 变压器 局部放电 试验 transformer partial discharge test