论述了正确选择母差保护CT中性点接地点的重要性,接地点选择不当,有可能造成保护误动,母差保护接地点应选择在控制室一点接地。
This paper discussed the importance of proper selection of the earth point of CT neutral point. If the earth point Selected is not appropriate, it may be cause the protection act in error. We ought to select the earth point of the busbar differential protection in one point where located the control-room.