摘要 从变压器短路后的分析入手,提出了几种检查和检测变压器绕组变形的方法,综合分析各种方法的优缺点后提出,频率响应分析技术是当前测量变压器绕组变形的最有效工具。并以承德供电公司西地站#1主变发生绕组变形的诊断实例为依据,说明开展频率响应法测量变压器绕组变形的有效性和必要性。 Starting with the analysis of the short - circuited transformer, this paper puts forward a couple of methods of inspecting and testing the transformer with the winding deformation. With the synthetical analysis of the advantages and disadvantages of different methods, the paper points out that the technique of the analysis of frequency responding is nowadays the most effective method to measure the transformer with winding deformation. Based on the diagnosed sample from Xidi No. 1 station's major transformer in Chengde Power Supply Company, this paper proves the effectiveness and necessity of carrying out the frequency responding to measure the transformer with winding deformation.
机构地区 承德供电公司
出处 《承德石油高等专科学校学报》 CAS 2007年第4期33-37,共5页 Journal of Chengde Petroleum College
关键词 变压器 绕组变形 频率响应 检测 transformer winding deformation frequency responding inspection and testing
  • 相关文献

参考文献3

  • 1陈化刚.电力设备预防性试验方法及其诊断技术[M].北京:中国电力出版社,2001.
  • 2陈化刚.电力设备预防性试验技术问答[M].北京:中国水利水电出版社,1998.
  • 3华北电力科学研究院.变压器绕组变形测试技术应用导则[S].北京:华北电力集团公司,1999.