摘要
根据转子接地保护的原理及轴电压的形成,阐述了转子1点接地保护误动与轴电压、大轴接地之间的关系。通过浙江兰溪发电厂4×600MW机组转子1点接地保护为例对转子接地误动进行分析,并建议将发电机大轴接地铜辫改为接地碳刷形式,保证大轴接地的可靠。
Based on prineiples of rotor grounding protection and formation of shaft voltage, this paper explains relationships between rotor point 1 grounding protection misoperation with shaft voltage and main shaft grounding. Using Lanxi Power Plant 4×600 MW unit rotor point 1 grounding protection as an example, this paper analyzes rotor grounding protection misoperation and suggests that carbon brush should replace copper braid in main shaft grounding to improve reliability.
出处
《电力建设》
2008年第1期69-70,共2页
Electric Power Construction
关键词
轴电压
转子接地保护
励磁
shaft voltage
rotor grounding protection
excitation