期刊文献+

我国火电基地串补输电系统的次同步谐振问题 被引量:48

SSR Problem in Compensated Transmission System of Thermal Power Bases in China
下载PDF
导出
摘要 分析了不同装机容量和不同输送距离下火电基地的输电能力及其所需的固定串补配置,并采用特征值分析方法对串补可能引发的次同步谐振(sub-synchronons resonance,SSR)进行了评估。结果表明,当火电基地装机容量大于2000MW,输送距离在400km以上,串补度在30%~50%时,将面临不同程度的SSR威胁。装机容量愈大,输电距离愈长,要求串补度愈高,SSR的危害愈严重。 The transfer capability of thermal power bases under different installed capacities and transmission distances as well as its required fixed series compensation (FSC) are analyzed. By means of eigenvalue analysis the sub-synchronous resonance (SSR) that may cause by series compensation is evaluated. Analysis results show that the thermal power base will face with different extent of SSR risk while the installed capacity of thermal power base is more than 200MW, the transmission distance is longer than 400kin and the series compensation ratio is between 30 percent and 50 percent. With the increment of installed capacity, transmission distance and series compensation level, the damage of SSR will be more serious.
出处 《电网技术》 EI CSCD 北大核心 2008年第1期5-8,19,共5页 Power System Technology
基金 国家重点基础研究发展计划项目(973项目)(2004CB217906)。~~
关键词 火电基地 输电能力 次同步谐振 特征值分析 thermal power base transfer capability sub-synchronous resonance (SSR) eigenvalue analysis
  • 相关文献

参考文献17

二级参考文献51

  • 1张帆,徐政.TCSC对发电机组次同步谐振阻尼特性影响研究[J].高电压技术,2005,31(3):68-70. 被引量:29
  • 2杨帆,王西田,陈陈.串联补偿输电系统次同步谐振的电气模态阻尼的参数敏感性分析[J].华东电力,2005,33(6):22-27. 被引量:11
  • 3傅霞飞.紧凑型线路的理论和实践[J].电力技术,1991,2:43-48.
  • 4吴维韩 薛家骐.苏联输电线路中应用紧凑型技术的研究[J].高电压技术,1989,4:15-18.
  • 5赵贺 周孝信.可控串补触发级抑制次同步谐振的方法研究报告[M].中国电力科学研究院,1997,11..
  • 6-.伊冯500kV可控串补TNA模拟试验研究技术总结报告[M].中国电力科学研究院,1999,10..
  • 7张Zhe.可控串补抑制次同步谐振的仿真分析研究[M].,1999,8..
  • 8赵学强.串联补偿系统的次同步振荡分析和可控串联补偿方案的研究[M].上海:上海交通大学,1997..
  • 9黄家裕,同步电机基本原理及其动态行为分析,1989年
  • 10团体著者,EMTP使用说明,1987年