DSP在电力系统实时相量测量的研究 被引量:1

Study of the real-time measurement of power system phasor based on DSP
下载PDF
导出
摘要 实时相量测量一直以来都是电力系统实现动态监测、保护及控制的难点,利用GPS技术的时钟信号的定时精度小于1μs,为DSP芯片TMS320LF2406A的电力系统相量测量建立相同的参考基准,对相应的实验数据进行分析,其测量精度较高、准确性较好,为电力系统快速的在线动态监控提供了重要依据,具有较好的应用价值。 The real-time measurement of phasor is a difficulty in power system dynamic monitoring, protecting and controlling. This paper uses GPS which can provide the clock signal times accuracy of less 1μ, to establish the same reference for measured TMS320LF2406A embedded DSP chip. The analyzed experimental data improves better precision and veracity, It is a significant evidence for the power systems in rapid, on-line and dynamic monitoring-controlling, and is valuable for practical use. This project is supported by National Natural Science Foundation of China(No.50607007).
出处 《继电器》 CSCD 北大核心 2007年第24期40-42,47,共4页 Relay
基金 国家自然科学基金资助项目(50607007)~~
关键词 GPS 嵌入式DSP 离散傅立叶变换 实时相量测量 GPS embedded DSP chip discrete Fourier transform algorithm real-time phasor measurement
  • 相关文献

参考文献5

  • 1IEEE Working Group Reports.Synchronized Sampling and Phasor Measurements for Relaying and Control[J].IEEE Trans on PWRD,1994,9(1):442-449.
  • 2Stanton S E,et al.Application of Phasor Measurements and Partial Energy Analysis in Stabilizing Large Disturbance[J].IEEE Trans on Power Systems,1995,10(1):297-305.
  • 3Burnett R,et al.Power System Applications for Phasor Measurement Units[J].IEEE Computer Applications in Power,1994,(1):8-13.
  • 4张永建.电网监控与调度自动化[M].北京:中国电力出版社,2004
  • 5张雄伟,邹霞,贾冲.DSP原理与应用[M].北京:机械工业出版社,2005.