摘要
配电系统的10(6)kV变压器通常是三角形接线,无中性点,通过分析电网在发生单相接地故障时的电流分布,得出装设接地变压器进行中性点经消弧线圈(或小电阻)接地的必要性,并简单介绍了接地变压器结构和容量的选择方法。
Usually, 10(6)kV transformer in distribution system is triangular wiring, there are not neutral point, by analyzing the current distribution when single phase earth fault of power grid, come to the necessity of install grounding transformer neutral through Petersen coil (or low resistance)for grounding, and summarizes the way of selecting structure and capacity selection for the grounding transformer.
出处
《广东输电与变电技术》
2008年第1期40-42,共3页
Guangdong Power Transmission Technology
关键词
单相接地故障
接地变压器
接地变压器的容量
Single phase earth fault Grounding transformer Capacity of grounding transformer