期刊文献+

交流接触器在不同使用类别下的额定工作电流分析 被引量:2

Rated Working Current of AC Contactor under Different Use Categories
下载PDF
导出
摘要 交流接触器在不同的使用类别情况下,应规定不同的额定工作电流。分析了4种使用类别下的使用情况,从实际负载起动电流去探求AC-4的额定工作电流。还分析了其他几个影响额定工作电流的因素。经分析得出,如果电压、功率因数、操作频率、负载因数等其他相关因素比一般情况更加恶劣,应将Ie4与Ie3的比值再适当减小一些。 Under different use categories, AC contactor should be regulated with different rated working current. Analysis was made to use conditions of 4 kinds of categories, the rated working current of AC-4 should be found out from actual load start current. Analysis was also made to several factors which have impacts on rated working current. After analysis, it is found if voltage, power factor, operating frequency, load factor ere other related factors are much worse than normal conditions, so the ratio of Ie4 and Ie3 should be suitably reduced a little.
作者 姜梅生
出处 《江苏电器》 2008年第1期34-37,共4页
关键词 交流接触器 使用类别 负载起动电流 额定工作电流 负载因数 AC contactor use category load start current rated working current load factor
  • 相关文献

同被引文献5

  • 1施耐德电气.Multi9系列低压终端配电系统综合样本[M],2008.
  • 2施耐德电气.Tesys系列电动机起动与保护[M],2008.
  • 3上海电器科学研究所(集团)有限公司,上海电器股份有限公司人民电器厂,常熟开关制造有限公司,等.GB14048.4-2010低压开关设备和控制设备第4-1部分:接触器和电动机起动器机电式接触器和电动机起动器(含电动机保护器)[S].北京:中国标准出版社,2011.
  • 4施耐德电气.电气装置应用(设计)指南[M].第二版.北京:中国电力出版社,2008.
  • 5林荔荔.电气设计中低压交流接触器的选用[J].内蒙古石油化工,2009,35(1):81-82. 被引量:1