期刊文献+

关于发电机转子接地保护几个问题的探讨 被引量:40

Study on Issues of Generator Rotor Earth Fault Protection
下载PDF
导出
摘要 分析了轴电压吸收回路以及接地碳刷与大轴间接触电阻对发电机转子接地保护的影响,并分别提出了相应的对策和注意事项。可通过延长电子开关切换周期或方波电源周期消除轴电压吸收回路的影响,应保持接地碳刷与转子大轴间接触良好。探讨了旋转励磁机组转子接地保护的构成方式,建议采用定期检测方式。 This paper analyzes the influences of shaft voltage absorbing circuit and brush touching of generator rotor earth fault protection. Some countermeasures and advices are presented resistance on the performance Prolonging period of electric switches and injected square voltage is suggested to eliminate the influence of shaft voltage. It is necessary for rotor earth fault protection to keep good-touching of grounding brush and rotor shaft. Rotor earth fault protection configuration of revolving excitation generator is investigated subsequently, and periodical detecting mode is commended.
出处 《电力系统自动化》 EI CSCD 北大核心 2008年第1期90-92,102,共4页 Automation of Electric Power Systems
关键词 转子接地保护 轴电压吸收回路 接地碳刷 接触不良 旋转励磁 rotor earth fault protection shaft voltage absorbing circuit grounding brush bad-touching revolving excitation
  • 相关文献

参考文献3

二级参考文献3

  • 1电力工业部安全监察及生产协调词组.新编保护继电器校验[A].北京:中国电力出版社,1997..
  • 2李骏年.电力系统继电保护[M].北京:中国电力出版社,..
  • 3国家电力调度通信中心.电力系统实用技术问答[A].北京:中国电力出版社,..

共引文献26

同被引文献125

引证文献40

二级引证文献92