期刊文献+

10~35 kV中性点非直接接地系统分相接地电容测试方法 被引量:3

Measurement of Split-phase Earthing Capacity for 10~35 kV Neutral Point Indirect Earthing System
下载PDF
导出
摘要 10~35 kV电压等级电力系统一般根据单相接地电容电流的大小来防治弧光接地电压,因此须测量中性点非直接接地系统分相接地电容的大小。笔者介绍了利用偏置电容测量中性点非直接接地系统分相接地电容的方法,并分析获得了理论计算公式;把实际系统参数代入公式计算并与测试数据对比,表明该方法简单,数值计算准确,可不中断对用户供电,具有广阔的推广应用前景。 10-35 kV voltage grade power system prrvent the arc overvoltage generally based on the size of single-phase current to the ground capacitor. So split-phase ground capacitor size of neutral point indirect earthing system needs to be measured. The measurement of split-phase earthing capacity for neutral point indirect earthing system via bias capacitor was introduced. The computing formula was obtained through analysis, and the actual system parameters were used for calculation. Compared with the test data, the calculated result proves that the measurement is simple and accurate without interrupting power supply to users.
作者 侯崇升
出处 《高压电器》 CAS CSCD 北大核心 2008年第1期81-83,共3页 High Voltage Apparatus
关键词 接地电容 偏置电容 测量 ground capacitor bias capacity measurement
  • 相关文献

参考文献4

二级参考文献16

共引文献61

同被引文献12

引证文献3

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...