期刊文献+

小电流接地系统单相接地故障的模糊选线新方法

A New Fuzzy Fault Line Selection Method of Non-Solid Earthed Power System
下载PDF
导出
摘要 基于单相接地故障发生后暂态零序电流含有大量丰富的高次谐波成分的现象,利用各线路故障暂态时期零序电流中高次谐波的衰减速率作为新选线依据,并结合应用模糊信息融合原理,将此新方法与残流变化量比较法相结合提出了一种新的模糊综合选线判据,构造了形式简洁物理意义清晰的的故障隶属函数。进行动模实验检验,实验运行结果表明该判据选线正确,抗干扰能力强,是针对现有单相接地故障选线判据适应性较差、正确率不高的现状一种有效实用的综合选线判据。 If a single-phase fault occurs in a distribution system, both the faulted line and the healthy line all have high frequency transient component. A new scheme of line selection about earth fault diagnosis in the networks based on decaying high frequency component and residual current method with fuzzy information fusion is proposed. This methcd proposes more simple and concision subordinate function for integrate line selection. A sample selection platform has been built to test the method,and the operation results showed the new method's excellent disturbance-proof ability which is ideal for fault line selection.
作者 胡佐
出处 《华北电力技术》 CAS 2008年第2期24-27,共4页 North China Electric Power
关键词 高次谐波衰减 衰减速率 模糊信息融合 综合选线判据 decaying high frequency component decaying speed fuzzy information fusion integrate line selection
  • 相关文献

参考文献7

二级参考文献18

  • 1桑在中,张慧芬,潘贞存,田质广.用注入法实现小电流接地系统单相接地选线保护[J].电力系统自动化,1996,20(2):11-12. 被引量:136
  • 2李哈乞夫(苏联) 吴维诚等(译).消弧设备的选择、装设和运行[M].北京:电力工业出版社,1956..
  • 3王秉钧.太原供电局城北变电站事故分析报告[M].,1997..
  • 4西安交通大学高压技术教研组.过电压及其保护[M].西安:西安交通大学出版社,1961.461.
  • 5藤泽孝道(日本).20kV级配电设备的绝缘协调[J].电 评论,2000,(9).
  • 6何奔腾,中国电机工程学报,1997年,3期
  • 7何奔腾,1994年
  • 8李福寿,中性点非有效接地电网的运行,1993年
  • 9何奔腾,电力系统及其自动化学报,1992年,6卷,1期
  • 10黄焕琨(译),计算机继电保护系统,1983年