期刊文献+

排管敷设情况下电缆额定载流量研究之一——载流量试验研究 被引量:11

Study on the Ampacity of Cables Installed in Pipes,Part One—Theoretic Calculation of Ampacity
下载PDF
导出
摘要 介绍了模拟南京地区110kV交联聚乙烯(XLPE)电缆排管敷设情况下的单回路和双回路两种情况下载流量试验,对试验装置、试验线路设计及试验结果都进行了详细的叙述。提出了双回路比单回路电缆载流量下降16%~17%,同时对今后的电缆敷设线路设计中应注意的问题提出了建议。 An imitation-test of the ampacity of a simple circuit and a double circuit 110 kV XLPE cables installed in pipes in the Nanjing area was carried out, The design of the test circuit and test results were described in detail. A conclusion of the test is that compared with the single circuit the ampacity in a double circuit decreases by 16% - 17%. Finally proposals as to the matters needing attention in the design of cable installation were put forward.
出处 《电线电缆》 2008年第1期16-20,25,共6页 Wire & Cable
关键词 交联聚乙烯电力电缆 排管敷设 载流量 试验研究 XLPE power cable installation in pipes ampacity study by test
  • 相关文献

参考文献2

二级参考文献2

共引文献6

同被引文献63

引证文献11

二级引证文献61

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部