摘要
介绍了模拟南京地区110kV交联聚乙烯(XLPE)电缆排管敷设情况下的单回路和双回路两种情况下载流量试验,对试验装置、试验线路设计及试验结果都进行了详细的叙述。提出了双回路比单回路电缆载流量下降16%~17%,同时对今后的电缆敷设线路设计中应注意的问题提出了建议。
An imitation-test of the ampacity of a simple circuit and a double circuit 110 kV XLPE cables installed in pipes in the Nanjing area was carried out, The design of the test circuit and test results were described in detail. A conclusion of the test is that compared with the single circuit the ampacity in a double circuit decreases by 16% - 17%. Finally proposals as to the matters needing attention in the design of cable installation were put forward.
出处
《电线电缆》
2008年第1期16-20,25,共6页
Wire & Cable