摘要
电网中性点采用经消弧线圈并电阻接地,可借电阻接地之长弥补消弧线圈接地之短,有效地抑制电弧接地过电压,使正常运行时的中性点位移电压不致过大。在这种接地方式下,利用计算机对消弧线圈进行控制,使其根据电网总电容电流的大小自动跟踪补偿。
The power network′s neutral point can suppress the arc-earthing over-voltage effectively when it is grounded through an arc-extinguishing coil.Further, if it is grounded through the arc-extinguishing coil of automatic tracking compensation(paralleling it with a resistance),it can overcome the defects of the above earthing mode,and canreduce the arc-earthing over-voltage to a lower value.
出处
《华北电力大学学报(自然科学版)》
CAS
北大核心
1997年第3期50-55,共6页
Journal of North China Electric Power University:Natural Science Edition
关键词
消弧线圈
中性点
电网
接地方式
arc-extinguishing coil
neutral point