期刊文献+

直流侧并联型有源电力滤波器的可控性及其统一控制策略 被引量:11

The Controllability of Parallel DC Side Active Power Filter and Unified Control Strategy
下载PDF
导出
摘要 直流侧并联型有源电力滤波器并联在整流桥的直流侧,实现谐波治理的功能。本文提出了直流侧并联型有源电力滤波器正常工作的两个可控性条件,一是有源滤波器可以控制为一个受控电流源,二是有源滤波器的输入平均功率为零才能保证在逆变器直流侧选用无源储能元件。根据提出的两个条件分别分析验证了单相和三相直流侧有源电力滤波器的可控性。根据单相和三相直流侧有源电力滤波电路功能上的相似性,提出了基于单周控制的无需进行谐波电流检测的统一控制策略,稳态和动态实验结果证明了统一控制策略的正确性。 DC side active power filter which is paralleled in dc side of rectifier can suppress the input harmonic current of the rectifier. Two controllability conditions which ensure the operation of dc side active power filter(APF) are proposed. The first one is that dc side APF should be controlled to a controlled current source, and another one is that the average input power of APF should be zero, and the second one makes it possible to use the passive energy storage element. According to the proposed controllable conditions, the controllability of single-phase and three-phase dc side APF is analyzed. A unified control strategy based on one cycle control is proposed to control the single-phase and three-phase dc side APE By using one-cycle control, there is no need to sense and calculate the harmonic current components. The steady and dynamic experimental results verified the correctness of the control strategy.
出处 《电工技术学报》 EI CSCD 北大核心 2008年第2期127-132,共6页 Transactions of China Electrotechnical Society
基金 国家自然科学基金(50507020) 重庆市科委自然科学重点基金(2005BA6017)资助项目
关键词 整流桥 有源电力滤波器 可控性 控制策略 Rectifier, active power filter, controllability, control strategy
  • 相关文献

参考文献7

二级参考文献22

  • 1刘进军,刘波,王兆安.基于瞬时无功功率理论的串联混合型单相电力有源滤波器[J].中国电机工程学报,1997,17(1):37-41. 被引量:85
  • 2Luowei Zhou, Keyue M.Smedly .Unified constant faequency integration control of active power filters[A]. APEC2000[C]: 406-412.
  • 3Keyue M. Smedly, Luowei Zhou, Chonqming Qiao. Unified constant frequency integration con~ol of active power filters-steady-state and dynamics [J].IEEE Trans. Power Electron, 2001,16(5): 428-436.
  • 4Wenkai Wu, Weihong Qiu, Rustom, K, et aL Universal input single-stage PFC AC/DC converter with reduced DC-bus voltage stress[A].IEEE PESC[C]. 2002: 1351-1356.
  • 5Shiguo Luo, Huai Wei, Guangyong Zhu, et al. Several schemes of alleviating bus voltage stress in single stage power factor correction converters[A]. IEEE PESC[C],1999: 443-448.
  • 6Habrouk M EI, Darwish M K, Mehta P. Active power filters: A Review. IEE Proc. Electr. Power Appl.,2000, 147 (5) :403--413.
  • 7Zhou Luowei, Li Zicheng. A novel active power filter based on the least compensation current control method.IEEE Trans. Power Electron., 2000, 15 (4): 655-659.
  • 8Hideaki Fujita, Takahiro Yamasaki, Hirofumi Akagi. A hybrid Active filter for damping of harmonic resonance in industrial power systems, IEEE Trans. Power Electron.,2000, 15 (2): 215--222.
  • 9Ali Dastfan, Victor J Gosbell, Don Platt. Control of a new active filter using 3-D vector control, IEEE Trans.Power Electron., 2000, 15 (1): 5--12.
  • 10Zhou Luowei, Keyue M. Smedly. Unified constant-fre-quency integration control of active power filters, APEC 2000:406--412.

共引文献349

同被引文献109

引证文献11

二级引证文献99