预防220kV变压器受短路冲击损坏事故的一种措施 被引量:3

Study and Application on Measures for Protecting 220 kV Transformer from Short-Circuit Faults
下载PDF
导出
摘要 当220kV变电站的110kV侧发生单相接地故障时,有可能造成主变压器遭受冲击而损坏。通过分析变压器绕组的抗短路能力,发生单相接地故障时流入变压器的短路电流,可知国产老旧变压器极易受到短路电流的冲击而损坏。文章以唐山供电公司的3个变电站为实例,介绍了一种通过改变主变压器中性点的接地方式,即在主变压器110kV中性点加装小电抗器,减小单相故障时的接地短路电流及流入主变压器绕组的短路电流,从而保护主变压器的措施,改造的效果是比较好的。 The main transformer in 220 kV substation may be damaged by short circuit current, when there is a single-phase grounding fault occurred in the 110 kV Side. Through analyzing the short-circuit withstand ability of transformer winding and the short-current that feed into the transformer, it is found out that the old transformers can be damaged easily by single-phase grounding fault. Taken three substations in Tangshan Power Supply Co. as an example, the paper introduced the measure to reduce the short-current that feed into the transformer when the single-phase gounding fault occurred, which is through changing the grounding mode of transformer neutral and adding small reactor in 110 kV neutral of main transformer. This measure can protect main transformers in 220 kV transformer substation effectively.
作者 王恒 黄方能
机构地区 唐山供电公司
出处 《电力设备》 2008年第3期65-68,共4页 Electrical Equipment
关键词 变压器 单相接地 小电抗器 transformer single-phase grounding small reactor
  • 相关文献

参考文献7

二级参考文献28

  • 1舒廉甫.500kV变压器中性点接地方式成果应用推广[J].高电压技术,1993,19(4):45-48. 被引量:14
  • 2舒廉甫.500kV变压器中性点接地方式[J].电力技术(北京),1989,22(3):36-41. 被引量:5
  • 3华东电力设计院.华东电网中长期电源规模优化、调峰规划及电网规划[J].-,1998,.
  • 4华北电力设计院.华北2010年电网规划[J].-,1997,.
  • 5中南电力设计院.华中电网2010年网络规划第5卷短路电流计算[J].-,1997,.
  • 6东北电力设计院.东北地区2010年电网发展规划[J].-,1997,.
  • 7甘肃省水利电力 西北电力设计院.电力系统规划设计手册[M].,1974..
  • 8河南电力试验研究所,国家电力公司武汉高压研究所.220kV变压器中性点采用小电抗器接地方式的研究总结报告[R].郑州:河南电力试验研究所,2000.
  • 9GB1094.5-2003,电力变压器第5部分:承受短路的能力[S].
  • 10华东电力设计院,华东电网中长期电源规模优化、调峰规划及电网规划,1998年

共引文献104

同被引文献35

引证文献3

二级引证文献21

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部