期刊文献+

火灾下防火涂料破损后约束柱的稳定承载力 被引量:12

Stability Capacity of Restrained Steel Columns after Damage of Fire Retardant Coating in Fire
下载PDF
导出
摘要 为考察地震破坏防火涂料后钢柱的抗火性能,根据势能驻值原理推导了约束钢柱两端防火涂料破损后稳定承载力计算方法。分别讨论了防火涂料的破损长度、钢柱的升温以及端部转动约束刚度对稳定承载力的影响。结果表明:破损长度对约束柱稳定承载力影响较大;温度较低时,温度对稳定承载力影响不大,而端部约束刚度对稳定承载力影响较大,温度超过500℃以后,温度对稳定承载力有较大影响,而转动约束刚度对稳定承载力影响变小。 In order to investigate the fire resistance of steel columns after damage of fire protection by earthquake, a method to predict the capacity for stability of restrained steel columns was proposed according to the principle of stationary potential energy. The influences of the length of fire retardant coating damage, column temperature and rotational restrained stiffness on capacity for stability of restrained steel columns were discussed. The results show that the damage length has a significant inflaence on the capacity for stability of rational restrained columns. Further more, when the temperature is low, the temperature has a small impact on the capacity for stability, but the rational restrained stiffness has great effect on the capacity for stability, when the temperature exceeds 500℃, the temperature will hav great impact on the capacity for stability and the rotational restrained stiffness will have little effect on the capacity for stability.
出处 《力学季刊》 CSCD 北大核心 2008年第1期120-126,共7页 Chinese Quarterly of Mechanics
基金 国家创新研究群体科学基金(50621062) 国家自然科学基金(50738005)
关键词 防火涂料 约束钢柱 稳定承载力 刚度 fire retardant coating restrained steel column capacity for stability stiffness
  • 相关文献

参考文献8

  • 1Tomecek D V, Milke J A. A study of the effect of partial loss of protection on the fire resistance of steel columns [J]. Fire Technology, 1993,29(1) : 4-21.
  • 2Ryder N L, Wolin S D, Milke, J A. An investigation of the reduction in fire resistance of steel columns caused by loss of spray-applied fire protection [J]. Journal of Fire Protection Engineering. 2002,12(1) : 31 - 44.
  • 3Milke J A. Analyses of the impact of loss of spray-applied fire protection on the fire resistance of steel columns. In: Davies D. Evans (Ed.)[C]. Fire Safety Science-Proceedings of the Seventh International Symposium, Worcester, USA, 2003.
  • 4Fontana M, Knobloch M. Fire resistance of steel columns with partial loss of fire protection [C]. In: Proccedings of the IABSE Symposium Shanghai 2004, Metropolitan Habitats and Infrastructure, IABSE Report Vol. 88, Shanghai, China, ISBN 3-85748-110-2, 2004, 352.
  • 5Kang Y, Hadjisophocleous G V, Khoo H A. The effect of partial fire protection loss on the fire resistance reduction of steel beams [C]. In: Fourth international workshop Structures in fire, Aveiro. Portugal, 2006, 63 - 74.
  • 6Stephen P I, Kihyon K, Byoung-Jun LEE. Fire load behaviour of steel building columns with damaged spray-applied fire resistive material[C]. In:Fourth international workshop Structures in fire, Aveiro, Portugal. 2006, 235- 245
  • 7Knobloch M, Raveglia E, Fontana M. Partial loss of fire protection and structural collapse of high-rise buildings[C]. In: International Congress Fire safety in tall buildings, University of Cantabria, Santander, Spain. 2006
  • 8中国工程建设标准化协会标准.建筑钢结构防火技术规范(CECS200-2006)[S].北京:2006.

同被引文献103

引证文献12

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部