通过一起220kV SF_6断路器合闸故障的排查,分析断路器BLG1002A操作机构的具体工作过程,尤其是分合闸掣子装置在分合闸中是如何配合工作的。并基于此对故障进行了原因分析及对故障操作机构进行了检修,检修的结果证明了分析的正确性,进而提出了改进措施。
By the checking an closing fault of 220kV SF6 circuit breaker and analysis the principle of BLG1002A operating mechanism, especially how to cooperation of the detent device during closing and opening. Based on it, carry on repairing for faulted operating mechanism, it indicates the analysis is correct, and put the improvement.
出处
《广东输电与变电技术》
2008年第2期19-20,共2页
Guangdong Power Transmission Technology
关键词
断路器
操作机构
掣子装置
合闸故障
Circuit breaker Operating mechanism Detent device Closing fault