期刊文献+

钢框架-混凝土核心筒结构框架地震设计剪力标准值研究 被引量:9

Study on Seismic Design Shear Force for Frame of Steel Frame-concrete Core Wall Structures
原文传递
导出
摘要 为研究双重体系钢框架-混凝土核心筒结构的框架设计地震剪力标准值,对20个钢框架-混凝土核心筒结构模型进行了静力弹塑性分析。从承载力、结构失效模式和框架破损程度三个方面评价20个计算模型的抗震能力。根据推覆分析结果,提出了如下设计建议:8度抗震设防时钢框架-混凝土核心筒结构的刚度特征值λ大于0.65,各层框架的设计地震剪力标准值不小于本层总剪力的18%和不小于框架-核心筒结构计算得到的地震剪力的1.2倍(加强层和顶层的剪力可不小于框架-核心筒结构计算得到的地震剪力),框架角柱轴压比不大于0.5。算例表明,符合建议的钢框架-混凝土核心筒结构,在地震作用时不会出现不合理的破坏形态。 To study seismic design shear force for steel frame of steel frame-reinforced concrete core wall structures, static elasto-plastic analysis (pushover analysis) of 20 structural models was conducted, The earthquake resistant capacity of the 20 structure models is evaluated by three aspects, i.e. , load-carrying capacity, structural failure mode and seismic damage index under structural failure state. It is recommended that for steel frame-reinforced concrete core wall structures the structural stiffness characteristic value should be larger than 0.65, the standard value of seismic design shear force of the steel frame should not be less than 18 % of the total storey shear and should not be less than 1.2 times of the frame shear obtained by analysis of steel frame-RC core wall structure (for the strengthen storey and the top storey, should not be less than the frame shear obtained by analysis of steel frame-RC core wall structure), the axial force ratio of comer steel columns should not be larger than 0.5. It is demonstrated by a calculation example that under earthquake excitations un-excepted failure mode would not occur for steel frame-RC core wall structures which satisfy the above requfrements.
出处 《建筑结构》 CSCD 北大核心 2008年第3期1-5,123,共6页 Building Structure
基金 国家科研院所技术开发研究专项资金资助项目2002
关键词 钢框架-混凝土核心筒结构 静力弹塑性分析 刚度特征值 框架设计地震剪力标准值 轴压比 steel frame-reinforced concrete core wall structure static elasto-plastic analysis structural stiffness characteristic value standard value of seismic design shear force steel frame axial force ratio
  • 相关文献

参考文献8

  • 1.高层建筑混凝土结构技术规程(JGJ3-2002)[S].北京:中国建筑工业出版社,2002..
  • 2.建筑抗震设计规范(GB50011-2001)[S].北京:中国建筑工业出版社,2001..
  • 3International Conference of Building Officials. 1997 Uniform Building Code [S]. UBC-1997, April 1997.
  • 4International Code Council. 2000 International Building Code [S]. IBC-2000, March 2000.
  • 5Computers and Structures, Inc. SAP2000 ANALYSIS REFERENCE, Volume 1 [R]. Berkeley, California, USA, 1997.
  • 6魏勇,钱稼茹.应用SAP2000程序进行剪力墙非线性时程分析[J].清华大学学报(自然科学版),2005,45(6):740-744. 被引量:11
  • 7Federal Emergency Management Agency. NEHRP Guidelines for the Seismic Rehabilitation of Buildings[S]. FEMA 273, October 1997.
  • 8钢结构设计规范(GB50017-2003)[S].北京:中国计划出版社,2003.

二级参考文献3

共引文献196

同被引文献73

引证文献9

二级引证文献43

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部