期刊文献+

双馈感应风电机组联网运行仿真及实证分析 被引量:26

Simulation and Experimental Analysis on the Grid Connected Doubly Fed Induction Generator Wind Turbines
下载PDF
导出
摘要 随着风电并网规模的不断扩大,风电功率波动对所接入电力系统调峰、调频等运行性能的影响将越加显著。为获得双馈感应风电机组联网运行特性并校验所建模型的有效性,进行了接于实际电力大系统的风电场短路试验。通过对实测数据的分析辨识出风电机组的动态特性;基于所建模型对短路试验进行了仿真重现。实测结果与仿真结果相吻合,验证了所建模型的有效性。 Large scaled wind power integration into power system increasingly imposes significant impacts on the system operations such as the peak load regulation and frequency regulation, To obtain the operational characteristics of doubly fed induction generators (DFIGs) and validate models, the short circuit testing on a grid connected wind farm was carried out, and the dynamic performance of DFIG was identified by the recorded field test data, Based on the established model, the short circuit tests were simulated and consistent results were obtained.
出处 《电力系统自动化》 EI CSCD 北大核心 2008年第7期87-91,共5页 Automation of Electric Power Systems
关键词 双馈感应发电机组 短路试验 撬杠保护 风力发电 doubly fed induction generator(DFIG) short-circuit experiment crow-bar protection wind generation
  • 相关文献

参考文献16

二级参考文献120

共引文献1569

同被引文献314

引证文献26

二级引证文献455

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部