期刊文献+

基于特定消谐技术的单相有源滤波器设计 被引量:3

A design of active power filter based on selective harmonic elimination technique
下载PDF
导出
摘要 设计了一种新型的单相有源电力滤波器(APF),应用特定消谐技术,不需实时检测负载的无功电流和高次谐波电流,即可实现同时补偿负载无功及高次谐波电流的需求。给出了一种优化特定谐波消除PWM技术开关角的求解方法;设计了单相有源电力滤波器PI控制器。仿真结果表明该滤波器具有响应速度快,稳定性好,能有效地消除和抑制谐波,并能够对无功功率进行灵活地调节等特点。 The paper designs a new type of single-phase active power filter(APF),By applying selective harmonic elimination technique ,the APF can compensate the reactive component and high harmonics of line current without detecting the reactive current and harmonic current of the load. A switch angle's solution method of optical SHEPWM is presented, PI controller of the APF is also designed. The simulation results show the APF has the advantages of fast resPonse time and good stability, effectively restraining and eliminating harmonics, and flexible regulation of reactive power.
出处 《继电器》 CSCD 北大核心 2008年第8期46-49,54,共5页 Relay
基金 吉林省教育厅科技资助项目(2006-023)
关键词 特定谐波消除PWM δ井目移控制 有源滤波器 SHE PWM δphase-shifting control active power filter
  • 相关文献

参考文献9

二级参考文献41

  • 1杨君,王兆安.三相电路谐波电流两种检测方法的对比研究[J].电工技术学报,1995,10(2):43-48. 被引量:131
  • 2李庚银,陈志业,丁巧林,王昕伟.dq0坐标系下广义瞬时无功功率定义及其补偿[J].中国电机工程学报,1996,16(3):176-179. 被引量:144
  • 3[1]Akagi H. New trends in active filter for power conditioning. IEEE Trans. Ind. on Application, 1996,32(6):1312~1322
  • 4[2]Moran A L, Dixon J W, Rogel R. A three-phase active power filter operating with fixed switch frequency for reactive power and current harmonic compensation. IEEE Trans. on Ind. Electron.,1995,42(4):402~408
  • 5[3]Luo Shiguo, Hou Zhencheng. An adaptive detecting methods for harmonic and reactive current. IEEE Trans on Industrial Electronics, 1995, 42(1):85~98
  • 6[6]Wang Qun, Wu Ning, Wang Zhaoan. A neuron adaptive detecting approach of harmonic current for APF and its realization of analog circuit. IEEE Trans on Instru. and Measure., 2001, 50(1):77~84
  • 7Thomas G Habetler. A Space vector-based rectifier regulator for AC/DC/AC converters. IEEE Transactions on Power Electronics, 1999,8 ( 1 ) : 30-36.
  • 8Namho Hur, Jinhwan Jung, Kwanghee Nam. Fast dynamic DC-link power balancing scheme for a PWM converter-inverter system. Industrial Electronics Society,IECON'99 Proceedings. The 25th Annual Conference of the IEEE,1999,2:767-772.
  • 9Jinhwan Jung. Sunkyoung Lim. Kwanghee Nam. A feedback linearizing control scheme for a PWM converter-inverter having a very small DC-link capacitor.IEEE Trans. Ind. Applicat ,1999,35(5) : 1124- 1131.
  • 10Sakui M,Fujita H,Shioya M. A method for calculating harmonic currents of three-phase bridge uncontrolled rectifier with DC filter. IEEE Trans. Ind. Eletron,1989,36 (3): 434 -440.