摘要 以500kV柳桂线倒塔事故段为例进行荷载模拟计算分析,得出在不同覆冰厚度时导地线和光缆断线原因,以及不均匀覆冰和覆冰断线工况下铁塔受力情况,由计算结果分析了该事故段铁塔倒塌的事故原因,并对500kV输电线路提出加固改造和系统规划建议。 The paper takes 500 kV Liu-gui line as an example, calculates simulative load of its tower collapses, analysises the breakage reason of transmission conductor and optical cable, researches on the mechanics characteristic of tower in irregular icing and transmission line breakage condition, finds the reason of tower collapses and gives suggestion that rebuilding measures of improving anti-ice ability of 220 kV transmission line in Guangxi according to the analysis results.
出处 《电网与水力发电进展》 2008年第4期9-14,共6页
关键词 输电线路 输电铁塔 覆冰 极限承载力 transmission line tower, ice coating ultimate loadcarrying capacity