期刊文献+

变压器的冷却控制在电力生产中的应用 被引量:2

The application of transformer's cooling control in power production
下载PDF
导出
摘要 基于某大型水电站主变压器正常运行时其冷却控制系统误发"主变冷却全停"信号,造成主变保护误动作。根据现场检查,缘由主变压器油面温度指示控制器温度模拟量输出值出现越限现象,致使冷却控制流程中的主变冷却全停程序启动造成。针对这一问题,对冷却控制流程作了修改和完善,确保了主设备安全、稳定运行。 In a large- scale hydropower station, the cooling control system sent a wrong signal "main transformer cooling system stop" when the main transformer is working normally and the wrong signal made the main transformer protection system to accomplish a wrong action. After the site investigation on the accident,the reason is that the analogue temperature output value of the main transformer's oil surface temperature indieation controller was over its limit value and then made the main transformer's cooling system stop program start. For this problem, the modification and perfection work to the cooling control process was done to make sure that the main equipment will run safely and stably in the future.
出处 《青海大学学报(自然科学版)》 2008年第1期15-18,共4页 Journal of Qinghai University(Natural Science)
关键词 主变压器 油面温度指示控制器 冷却控制程序 main transformer oil surface temperature indication controller cooling control proqram
  • 相关文献

参考文献2

  • 1瑞典AKM公司.AKM34系列油温度指示控制器产品说明书[Z].武汉:武汉工业出版社,2002.
  • 2施耐德电气公司.PLC编程软件PL7ProV4.2用户手册[Z].西安:西安电子出版社,2000.

同被引文献9

引证文献2

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部