期刊文献+

运行中氢冷发电机湿度的合理控制

Appropriate Control of the Humidity of H 2 in H 2 Cooled Generator During Operation
原文传递
导出
摘要 根据国外资料和国内有关机组的运行经验,指出了氢冷发电机不论在停机或运转工况下,机内相对湿度控制在50%以下是足够安全的。由于停机与带负荷运转时,机内温度可能有很大差异,同样含湿量(或同样露点)的氢气在高温环境下,对应的相对湿度较低温环境下为低。因此,规定停机与运转工况下,执行不同的露点限值是合理的。 According to the operating experience in home and abroad, the H 2 cooled generator will be in safety condition if the relative humidity in the generator is controlled under 50% weather in shut down or operating condition. Due to the large temperature difference in generator between shut down and operation condition. H 2 with the same moisture content (or the same dewpoint) at high temperature will have a lower corresponding relative humidity than that at low temperature. Consequently, it is reasonable to excecute different dewpoint limiting value under shut down and operating condition.
作者 杨新村
出处 《华东电力》 1997年第9期4-7,共4页 East China Electric Power
关键词 氢冷发电机 湿度 冷却介质 控制系统 H 2 cooded generator humidity dewpoint coolant risk evaluation