期刊文献+

昆明电网110kV母线分段运行与并列运行方式比较 被引量:3

Comparison and analysis of 110 kV bus segmentation and parallel operation in Kunming power grid
下载PDF
导出
摘要 昆明电网中的110kV变电站的高压侧母线的主接线方式为单母分段接线,主要有2种运行方式:并列运行和分段运行。对2006年昆明电网丰大运行方式下的2种母线运行方式下的电网的电压合格率,网损率和N-1开断校验等3个方面进行了计算,并根据计算结果比较分析了2种运行方式。较之并列运行,110kV汤池变母线分段运行方式下,电压越限的母线数目增多;电网网损率略低;分段运行方式下汤池1号主变压器开断,电压越限的母线数目增多。 Single bus segmentation operation is applied in 110 kV buses of Kunming power grid, which mainly includes subsection and parallel operation modes. From the three aspects of voltage qualification rate, losses and N-1 outage checkout, calculation and comparison analysis of the two operation modes were performed in Kunming power grid in 2006. The conclusion is that numbers of over or under voltages buses is increased, losses is slightly decreased when 110 kV bus of Tangchi transformer is under segmentation operation mode.
出处 《中国电力》 CSCD 北大核心 2008年第6期39-42,共4页 Electric Power
基金 国家自然科学基金资助项目(50347026 50467002) 云南省科技攻关资助项目(2003GG10) 云南省自然科学基金资助项目(2005F0005Z 2002E0025M 2004E0020M)
关键词 昆明电网 母线运行方式 分段运行 并列运行 Kunming power grid buses operation mode segmentation operation parallel operation
  • 相关文献

参考文献7

  • 1朱文涛,孙士云,刘宗兵,周艳平.昆明电网的N-1校验及分析[J].昆明理工大学学报(理工版),2007,32(3):76-79. 被引量:2
  • 2TAN J C, CROSSLEY P A, MCLAREN P G, et al. Sequential tripping strategy for a transmission network back-up protection expert system [J ]. IEEE Trans on Power Delivery, 2002,17 ( 1 ): 68-74.
  • 3REHTANZ C, BERTSCH J. A new wide area protection system [C ]// Proceedings of 2001 IEEE Porto Power Tech Proceedings, Sep. 10-13, 2001, Porto, Portugal.Piscataway, NJ, USA: IEEE, 2001,4: 6.
  • 4NOVOSEL D, BEGOVIC M, TAYLOR C, et al. Wide area protection and emergency control [C]// Proceedings of 1999 IEEE Power Engineering Society Winter Meeting, Jan. 31-Feb. 4, 1999, New York:IEEE, 1999,2: 917-918.
  • 5INGELSSON B, LINDSTROM P O, KARLSSON D, et al. Wide-area protection against voltage collapse [J]. IEEE Computer Applications in Power, 1997, 10(4): 30-35.
  • 6SERIZAWA Y, IMAMURA H, KIUCHI M. Performance evaluation of IP-based relay communications for wide-area protection employing external time synchronization [ C ]//Proceedings of 2001 IEEE Power Engineering Society Summer Meeting, Jul. 15-19, 2001, Vancouver,Canada. Piscataway, N J, USA: IEEE, 2001,2: 909-914.
  • 7SERIZAWA Y, IMAMURA H, SUGAYA N, et al. Experimental examination of wide-area current differential backup protection employing broadband communications and time transfer systems [ C ]// Proceedings of 1999 IEEE Power Engineering Society Summer Meeting, Jul. 18-22, 1999, Admonton, Canada. Piscataway, NJ, USA: IEEE, 1999,2:1070-1075.

二级参考文献8

共引文献1

同被引文献17

引证文献3

二级引证文献4

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...