期刊文献+

西安地铁2号线隧道通风系统设计 被引量:2

Tunnel Ventilation Design of Xi'an Metro Line 2
下载PDF
导出
摘要 通过使用美国交通部SES软件,对西安地铁2号线隧道通风的优化方案设计进行建模计算。以地铁运行远期条件作为计算依据,对隧道内的温度、换气量进行统计分析,得出其隧道内温度在38℃以内、换气次数在7次/h以上能满足设计要求的结论,并对隧道内的压力进行计算,为其他设计提供数据参考。 By adopting the SES software of the Ministry of Communications of USA, a model was built and computation was carried out for the tunnel ventilation optimizing project design of Xi' an Metro Line 2. According to the long -term operation condition of metro, the temperature inside the tunnel and ventilation were analyzed statistically. Results indicated that the temperature inside the tunnel will be within 38 ℃ and the number of ventilations will be over 7 tines per hour, meeting the design requirements. The atmosphere pressure inside the tunnel was also calculated which can be taken for reference by other similar designs.
出处 《都市快轨交通》 2008年第3期45-48,共4页 Urban Rapid Rail Transit
关键词 隧道通风 SES软件 区间换气量 逐时计算 屏蔽门 tunnel ventilation SES ventilation of transit tunnel calculation by time step platform screen door
  • 相关文献

参考文献4

  • 1[1]西安市城市快速轨道交通二号线(铁路北客站一韦曲)工程可行性研究报告[R].西安,2006.
  • 2[5]胡自林.中长公路隧道纵向通风计算与防灾研究[D].中南大学硕士学位论文长沙,2004.
  • 3[6]地铁热环境试验研究报告[R].北京:清华大学,2003.
  • 4[7]Cooper L Y.ASET-A computer program for calculating available safe egress time[J].Fire safety Journal,1985,9:29-45.