上海浦东国际机场二期用户空调变频冷(热)水泵运行的节能性分析 被引量:2

Energy efficiency analysis on variable frequency chilled/hot water pumps in Shanghai International Airport Terminal 2 building
下载PDF
导出
摘要 以该工程为研究对象,计算了全年空调负荷,探讨了多台表面式空气处理器并联时水系统负荷-流量特性,结合水泵选型及能耗计算软件ESP-PLUS,对用户侧冷(热)水泵变频运行的节能性进行了分析,得到了采用该节能措施可实现的最小节能率。 Taking the project as a study object, calculates the year-round 8760 hours cooling and heating loads of this building, and discusses the load-flow character of water system with two or more surface air handling units in parallel connection. Combined with water pump selecting and energy calculating software ESP-PLUS, analyses the energy saving potential of variable frequency chilled/hot water pumps in the project, and obtains the minimal energy saving ratio of this measure.
出处 《暖通空调》 北大核心 2008年第6期131-137,111,共8页 Heating Ventilating & Air Conditioning
关键词 变频水泵 节能分析 表面式空气处理器 负荷-流量特性曲线 variable frequency pump, energy efficiency analysis, surface air handling unit, load-flow character curve