基于PMU的可控串补技术在抑制区域功率振荡中的应用

Technology of Thyristor Control Series Compensation for Suppressing Power Oscillation Based on PMU
下载PDF
导出
摘要 互联区域联络线上的功率振荡一般是由于系统阻尼较弱或重负荷等原因造成的。改善系统的阻尼特性可以有效的预防或平息此类振荡。根据同步相量测量单元(PMU)所测得的转速、相角等信息,设计了联络线可控串补装置(TCSC)的控制器,用以加强互联两区域系统的阻尼。文中在一个简单的2区4机电力系统中,研究了采用基于广域测量信号的TCSC控制器。仿真效果说明了基于广域测量系统的区间阻尼控制能有效抑制区间低频振荡和提高互联系统的传输容量,而且可在工程上实现。 In general tie line oscillator of power system between interconnected areas is caused by under - damp or heavy load, preventing effectively and putting down it can be done by improving the system characteristic of damp. According to some information, speed of rotation, phase angle ete, measured by PMU, TCSC controller is designed for strength damp of linkage with interconnected areas. The effectiveness and correctness of this design is proved by simulation. The wide area controller is used in the study of system of four machines two areas. Artificial results show that damping control based on WAM suppress effectively power oscillation and improve the capacity of transmitting. It is feasible on the project.
机构地区 昆明理工大学
出处 《云南水力发电》 2008年第2期67-71,共5页 Yunnan Water Power
关键词 区域振荡 同步相量测量单元(PMU) 可控串联补偿(TCSC) 低频振荡 power oscillation Phase Measure Unit(PMU) TCSC low-frequency oscillation
  • 相关文献

参考文献10

  • 1况华,沈龙,李文云,赵书强.500kV罗马线低频振荡分析与探讨[J].四川电力技术,2003,26(6):17-19. 被引量:4
  • 2秦文萍,徐红利.“9.1”蒙西电网机组低频振荡现象分析[J].太原理工大学学报,2007,38(1):51-55. 被引量:5
  • 3党杰,刘涤尘,潘晓杰,邹江峰,雷庆生,王静.基于RTDS和PSASP的华中电网低频振荡研究[J].继电器,2006,34(13):33-37. 被引量:2
  • 4Chi-shan yu,Chih-wen liu.Apractical design of TCSC controllers for the inter-area transient stability control using real-time measurements[J].Power Engineering Society 1999 Winter Meeting,IEEE,Volume:1,On page(s):661-666vol.1.
  • 5谢小荣,肖晋宇,童陆园,韩英铎.采用广域测量信号的互联电网区间阻尼控制[J].电力系统自动化,2004,28(2):37-40. 被引量:111
  • 6D.Z.Fang,Xiao Dong.Oscillation transient energy function applied to the design of a TCSC fuzzy logic damping controller to suppress power system interarea mode oscillations[J].IEE Proc-Gener,Transm Distrib,Vol.150,No.2.March 2003.
  • 7Martins N,Pinto,H.J.C.P.,Paserba J.J.Using TCSC for line power scheduling and system oscillation damping-small signal and transien tstability studies[J].Power Engineering Society Winter Meeting,2000.IEEE,Volume 2,Issue,2000:1455-1461.
  • 8B.Kalyan Kumar,S.N.Singh and S.C.Srvastava.Placement of FACTS controllers using modal controllability indices to damp out power system oscillations[J].IETG ener.Trasm.Distrib.,2007,1,(2):209-217.
  • 9J.Machowski,J.W.Bialek.State-variable control of shunt FACTS devices ufsing phasor measurements[J].Electr.Power Syst.Res.(2007),doi:10.1016/j.epsr.2006.12.
  • 10R.Mohan Mathur,Rajiv K.Varma.基于晶闸管的柔性交流输电控制装置[M].徐政,译.北京:机械工业出版社,2005.

二级参考文献14

共引文献120

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部