期刊文献+

检测电缆附件局部放电内置传感器的特性分析 被引量:20

Performance analysis of inner sensors used for partial discharge detection in cable accessories
下载PDF
导出
摘要 针对高压交联聚乙烯(cross-linked polyethylen,XLPE)电缆的结构及其附件内部易出现绝缘缺陷而导致放电的特点,基于电容耦合原理研制出用于电缆附件局部放电(partialdischarge,PD)信号检测的宽频带电容型内置传感器,通过建立传感器特性分析的电路模型,全面分析了影响传感器性能的各个因素,对其响应的频率特性进行了实测,并在实验室110 kV XLPE电缆PD试验平台上对电缆接头内部沿固体复合介质表面产生的放电进行试验研究。测试结果表明:研制的内置电容型传感器频率响应特性优异,能传感纳秒级暂态脉冲信号,其有效频带达500 MHz,可以用于XLPE电缆及附件PD超高频(Ultra-high frequency,UHF)信号的检测。 The structure of high voltage cross linked polyethylene (XLPE) cable and the characteristics of partial discharge (PD) mean that such discharges are very likely to happen in cable accessories due to insulation defects. The authors designed a wideband inner capacitive coupler for PD detection in cable accessories, and analyzed the characteristics of the coupler using an equivalent circuit model. The frequency response characteristics of the coupler were measured by square wave response. In addition, the measured results of the surface discharge produced along the dielectric interface in joints are given in 110 kV XLPE cable accessories. It is shown that the couplers work well in bands up to 500 MHz and can detect nanosecond transient pulse signals effectively. The couplers are available for ultra-high frequency (UHF) measurement of PD in cables and cable accessories.
出处 《重庆大学学报(自然科学版)》 EI CAS CSCD 北大核心 2008年第7期760-765,共6页 Journal of Chongqing University
基金 重庆市自然科学基金重点资助项目(CSTC 2006BA3018)
关键词 交联聚乙烯电缆 电容型传感器 局部放电 频率响应 超高频 cross-linked polyethylene cable capacitive coupler partial discharge frequency response ultra-high frequency
  • 相关文献

参考文献16

  • 1罗俊华,邱毓昌,杨黎明.10kV及以上电力电缆运行故障统计分析[J].高电压技术,2003,29(6):14-16. 被引量:194
  • 2李华春,周作春,陈平.110 kV及以上高压交联电缆系统故障分析[J].电力设备,2004,5(8):9-13. 被引量:44
  • 3蒋佩南.国产交联聚乙烯电力电缆击穿故障的评定和分析[J].电线电缆,2007(2):1-5. 被引量:23
  • 4AMETANI A, MIYAMOTO Y, NAHAOKA N. Semiconducting layer impedance and its effect on cable wave-propagation and transient characteristics [ J ]. IEEE Transactions on Power Delivery, 2004, 19 (4):1523-1531.
  • 5BOGGS S, PATHAK A, WALKER P. Partial discharge ⅩⅫ: high frequency attenuation in shielded solid dielectric power cable and implications thereof for PD location [J]. IEEE Electrical Insulation Magazine, 1996, 12(1): 9-16.
  • 6STEINBRICH K. Influence of semiconducting layers on the attenuation behaviour of single core power cables [J]. IEE Proceedings: Generation, Transmission and Distribution, 2005, 152 (2): 271-276.
  • 7VAKILIAN M, BI.ACKBURN T R, JAMES R E, et al. Semiconducting layer as an attractive PD detection sensor of XLPE cables [ J ]. IEEE Transactions on Dielectrics and Electrical Insulation, 2006, 13(4):885-891.
  • 8POMMERENKE D, STREHL T, HEINRICH R, et al. Discrimination between internal PD and other pulses using directional coupling sensors on HV cable systems[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1999, 6 (6): 814-824.
  • 9TIAN Y, LEWIN P L, DAVIES A E, et al. Partial discharge detection in cable using VHF capacitive couplers[J]. IEEE Transaction on Dielectrics and Electrical Insulatio, 2003, 10(2): 343-353.
  • 10徐阳,钟力生,曹晓珑,G CHEN,Jason Y TIAN,A E DAVIES.XLPE电缆及接头局部放电的超高频测量与分析[J].电工电能新技术,2002,21(1):5-8. 被引量:31

二级参考文献43

  • 1韦斌,王伟,李成榕,李信,李华春.VHF钳型传感器在线检测110kV XLPE电缆局放[J].高电压技术,2004,30(7):37-39. 被引量:34
  • 2Junhua Luo, et al. Study on surface discharge of composite dielectric in XLPE power cable joints[A]. 25th Anniversary Electrical Insulation Conference [ C ].Cincinnati, USA, 2001.
  • 3严璋.电气设备在线检测技术[M].北京:中国电力出版社,1995..
  • 4刘耀南 邱昌容.电气绝缘测试技术[M].北京:机械工业出版社,1990..
  • 5Ginzo Katsuta, Atsushi Toya, Keiichi Muraoka, et al, Development of a method partial discharge detection in extra-high voltage cross-linked polyethylene insulated cable lines[J]. IEEE Trans on Power Delivery, 1992. 7(3): 1068-1074
  • 6Wenzel D, Schichler U, Borsi H, et al. Recognition of partial discharges on power units by directional coupling[C]. The 9th ISH. Austria, 1995,5626: 1-4
  • 7Borsi H, G-ockenbach E, Schichler U. Monitoring of partial discharges (PD) in high voltage cables[C] The 8th ISH. Japan, 1993: 173-176
  • 8Wouters P A A F, Vanderlaan P C T, Hetzel E, et al. New on-ine partial discharge measurement technique for polymer insulated cables and accessories[C]. The 8th ISH. Japan, 1993:105-108
  • 9IEC60270. Partial discharge measurements[S], 1981
  • 10JuddMD, Farish O, PearsonJS, et al. Dielectric windows for UHF partial dischage detection[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2001, 8(6): 953-958.