800kV气体绝缘金属封闭输电线路及竖井安装 被引量:15

800 kV gas insulated transmission line in a vertical shaft
下载PDF
导出
摘要 气体绝缘金属封闭输电线路(GIL)因其传输容量大、可靠性高、电磁兼容性好等优点,正在广泛地应用于核电站、城市输电和大型水电站等场合。对于500kV及以上电压等级,1回GIL的输送容量相当于同电压等级的交链聚乙烯(XLPE)电缆两三回的输送容量。对拉西瓦水电站800kV GIL的结构、设计、制造及安装调试等特殊问题进行了介绍。特别对高海拔(2450m)、高落差(207m)场合(例如竖井中)安装GIL,给出了一些建议。对比发现,GIL与传统的电缆及全封闭组合电器(GIS)母线相比,在可靠性及经济性上有一定的优越性。 Because of high reliability, high power transfer capacity and good EMC, gas insulated transmission lines (GILs) are now widely used in nuclear power stations, city center substations and underground transmission lines, as well as large hydropower stations. For 500 kV and above, one loop GIL has 2 to 3 times of transfer capacity of a XLPE cable. This paper introduced particular issues of a 800 kV GIL in construction, design, manufacturing, erection and commissioning at Yellow River' s Laxiwa hydropower station with recommendations given for the GIL application in a high fall vertical shaft (207 m) and high altitude region (2 450 m). After comparison, GILs show the advantages than normal cables or GIS bus ducts in reliability and economy.
机构地区 美国AZZ/CGIT公司
出处 《中国电力》 CSCD 北大核心 2008年第8期44-47,共4页 Electric Power
关键词 气体绝缘金属封闭输电线路(GIL) 竖井安装 拉西瓦水电站 gas insulated transmission line (GIL) vertical shaft application Laxiwa hydropower station
  • 相关文献

参考文献4

二级参考文献14

  • 1G.Schoeffner,T.Neumann.气体绝缘管道输电线和气体绝缘组合电器在电厂中的应用[J].电力建设,2004,25(6):4-7. 被引量:21
  • 2杨百军.SF6 CGIT在岭澳核电站的应用[J].水电电气,2002,(1):118-124.
  • 3Y Watanabe, S Moil et al. Construction of First Gas Insulated Transmission Line in Japan[J]. IEEE Trans. PAS, 1981, PAS-100 (10): 4319-4329.
  • 4Thomas Hillers, et al. Gas Insulated Transmission Lines[J]. IEEE Power Engineering Review, 2000(9) : 15-16.
  • 5IEC 61640-1998,Rigid high-voltage, gas-insulated transmission lines for rated voltage of 72.5 kV and above [ S ].
  • 6压缩气体绝缘输电管道系统[R].美国CGIT Westhoro公司,2004.
  • 7ALTER J, AMMANN M, BOECK W, et al. N2/SF6 gas-insulated line of a new GIL generation in service [ C ]//CIGRE, 2002:21-204.
  • 8Influence of GIL and cable to power system[ R ]. CGIT Westhoro Company of USA, 2004.
  • 9TANIZAWA K, MINAGUCHI D, HONAGA Y. Application of gas insulated transmission line in Japan [ C ]//CIGRE,1984: 21-05.
  • 10NOJIMA T, SHIMIZU M, ARAKt T, et al. Installation of 275 kV-3.3 km gas-insulated transmission line for underground large capacity transmission in Japan [C ]//CIGRE, 1998:21/23/33-01.

共引文献83

同被引文献113

引证文献15

二级引证文献129

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部