期刊文献+

电力机车过关节式电分相过电压研究 被引量:51

Research of Over-voltages of Electric Locomotive Passing the Articulated Phase Insulator
下载PDF
导出
摘要 电力机车通过关节式电分相时,多次发生过电压现象,导致牵引变电所跳闸,对接触网和牵引变电所的安全运行构成严重影响。电力机车通过关节式电分相时的等值电路模型是一个由电阻、电感和电容组成的高阶电路。当电力机车通过关节式电分相不同区段时,等值电路在结构上会发生变化,从而产生过电压。本文利用MATLAB/Sim Power Systems对电力机车通过关节式电分相的过程进行仿真,结合兰州铁路局组织的过电压试验统计结果,分析中性段产生过电压的原因,并提出抑制过电压的措施。仿真结果表明,阻容保护器能够有效地抑制电力机车通过关节式电分相时在中性段上产生的过电压。 Over-voltages frequently happen when the electric locomotive passes the articulated phase insulator, which causes tripping of substations and serious influence on safe operations of the overhead contact system and traction substations. The equivalent circuit model for the electric locomotive passing the articulated phase insulator is a high order circuit which is composed of resistances,inductances and capacitances. The equivalent cir- cuit changes its structure when the electric locomotive goes through different sections of the articulated phase insulator, and this leads to happening of over-voltages. In this paper, the MATLAB/SimPowerSystems are used to simulate the process of the electric locomotive passing the articulated phase insulator, the causes of gen- erating over-voltages in neutral sections are analyzed in combination with the statistical results of over-voltage tests organized by the Lanzhou Railway Administration, and measures for suppressing over-voltages are put forward. The simulation results show that the RC protective installation can effectively restrain over-voltages in neutral sections when the electric locomotive passes the articulated phase insulator.
作者 宫衍圣
出处 《铁道学报》 EI CAS CSCD 北大核心 2008年第4期103-107,共5页 Journal of the China Railway Society
关键词 关节式电分相 过电压 电力机车 articulated phase insulator over-voltage electric locomotive
  • 相关文献

参考文献2

二级参考文献2

共引文献36

同被引文献272

引证文献51

二级引证文献228

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部