期刊文献+

高精度变频恒温恒湿空调机运行特性的实验研究 被引量:4

Experimental Study on the Performance of an Inverter Constant Temperature and Humidity Air Conditioner with High Precision
下载PDF
导出
摘要 通过实验研究了高精度变频恒温恒湿空调机的运行特性,并制造了实验样机。样机的精度和性能实验测试结果表明:设计的高精度变频恒温恒湿空调机能实现环境温度控制精度±0.5-±0.3℃,相对湿度控制精度±3%。±2%RH,并且能够长时间稳定可靠运行。同时,该机器具有较高的能效比,与同能力的普通恒温恒湿空调机相比,其能效比可提高约12.3%,节能效果显著。 Performance research on an inverter constant temperature and humidity air conditioner with high precision is provided by experiment. And a correlative sample is developed. As a result, temperature control precision of the sample can arrive at ± 0. 5 -±0.3℃ and relative humidity control precision can arrive at ±3%RH - ±2%RH. And, the sample with good anti-disturb capability can stably operate for long time. At the same time, the sample is of high the energy efficiency ratio. Comparatively, the energy efficiency ratio the sample is about 12.3% higher than that of the conventional unit in the nominal working condition of Chinese National Standard.
出处 《流体机械》 CSCD 北大核心 2008年第8期50-53,78,共5页 Fluid Machinery
关键词 变频恒温恒湿空调机 高精度 节能 实验研究 inverter constant temperature and humidity air conditioner high precision saving-energy experimental study
  • 相关文献

参考文献4

二级参考文献11

  • 1彦启森.空调技术的发展与展望.全国暖通空调制泠1998年学术文集[M].北京:中国建筑工业出版社,1998..
  • 2经济体制改革研究院 等.中国国际竞争力发展报告(1997)[M].北京:中国人民大学出版社,1998..
  • 3彦启森,全国暖通空调制冷1998年学术文集,1998年
  • 4郑易生,深度忧患当代中国的可持续发展问题,1998年
  • 5吴元炜,暖通空调,1998年,28卷,1期
  • 6经济体制改革研究院,中国国际竞争力发展报告(1997),1998年
  • 7国家统计局工业交通统计司,中国能源统计年鉴(1991-1996),1998年
  • 8张祉祜.制冷原理与设备.2000.
  • 9电子工业部第十设计研究院.空气调节设计手册,1995.
  • 10吴元炜.我们专业面临的发展问题[J].暖通空调,1998,28(1):21-23. 被引量:4