SF_6气体分解组分的多功能试验装置研制 被引量:46

Device of SF_6 Dissociation Apparatus Under Partial Discharge and Gaseous Decomposition Components Analysis System
下载PDF
导出
摘要 GIS设备中局部放电(PD)的模式识别和放电量的定量检测是目前国内外研究的难点。为此,作者设计了一套用于SF6PD气体分解组分研究的多功能试验装置,重点介绍了装置的结构和主要部件的计算参数。初步试验研究表明:该装置能够产生PD并引起SF6分解,气体检测单元可有效检测SO2F2、SO2、CF4、空气、CO2等组分气体,检测结果与现有IEC和GB标准基本相符;能够在不同试验电压下,模拟各种PD,具有获取SF6气体分解组分、气敏传感器响应信号、微观放电图像、微观放电过程以及脉冲放电电流波形等多信息功能,从而为深入开展GISPD导致SF6分解组分的关联比对研究,最终为解决放电模式识别和放电量定量检测难题提供了综合试验研究手段。 Partial discharge (PD) in GIS can induce SF6to decompose. Research on the quantitative measurement of PD energy and mode recognition is somewhat difficult currently. In order to analyze the gaseous decomposed components of SF6 under PD, a multi-functional experiment platform is devised. This paper mainly introduces its structure and corresponding parameters. Practical experiments indicate that PI) can be induced and that the gaseous compo- nents such as SO2 F2 ,SO2 ,CF1 ,Air and CO2 can be detected by the devised gaseous component analysis unit. The result of experiment is consistent with the IEC and GB standards basically. Furthermore, kinds of PD can be simulated; comprehensive information about PD, such as the gaseous decomposed components, response signal of gas sensor, ultraviolet photon microgram and the discharge current pulse signal, can be acquired by the detecting units. In all, based on the platform, comprehensive experimental methods are available for in-depth research on the relation between PD and gaseous decomposed components, quantitative measurement of PD energy and mode recognition.
出处 《高电压技术》 EI CAS CSCD 北大核心 2008年第8期1583-1588,共6页 High Voltage Engineering
基金 国家自然科学基金(50577069) 973计划前期专项(2006CB708411)~~
关键词 SF6 局部放电 分解气体 组分检测 试验装置 GIS SF6 partial discharge decomposied gas gaseous component analysis apparatus GIS
  • 相关文献

参考文献16

  • 1IEC60480-2004 Guidelines for the checking and treatment of sulfur hexafluoride (SF6) taken from electrical equipment and specification for its re-use[S], 2004.
  • 2IEEE Standard C37. 122.1-1993 IEEE guide for gas-insulated substations[S], 1993.
  • 3Bargigia A, Koltunowicz W, Pigini A. Detection of parallel discharges in gas insulated substations[J]. IEEE Transactions on Power Delivery, 1992, 7(3): 1239-1249.
  • 4GB/T8905-1996六氟化硫电气设备中气体管理和监测导则[S].1996.
  • 5GB/T18867-2002电子工业用气体六氟化硫[S].2002.
  • 6Van Brunt R J. Production rates for oxy-fluorides SOF2, SO2F2 and SOF4 in SF6 corona discharges[J]. Journal of Research of the National Bureau of Standards, 1985, 90(3) : 229-253.
  • 7马虹斌,邱毓昌.SF_6及其混合气体的放电毒性污染物分析[J].环境工程,1996,14(4):46-48. 被引量:8
  • 8Piemontesi M, Zaengl W. Analysis of decomposition products of sulfur hexafluoride by spark discharges at different spark energies[C]// 9th International Symposium on High Voltage Engineering. Graz, Austria: Graz University of Technology, 1995: 1-4.
  • 9Sauers E, Ellis W, Christophorou L G. Neutral decomposition products in spark breakdown of SF6 [J]. IEEE Transactions on Electr Insul, 1986, EI- 21(2): 111-120.
  • 10Chu F Y. Gas analysis as a ciagnostic tool for gas-insulated equipment[C]// Fifth Int Symp on Gaseous Dielectrics. Knoxville, Tenn, USA: University of Tennessee, 1987.

二级参考文献4

共引文献16

同被引文献545

引证文献46

二级引证文献522

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部