深圳 10kV 配电网中性点经电阻接地的运行分析 被引量:2

The Operation Analysis of Neutral Grouding through Resistance in 10kV Power Distribution System in Shenzhen
下载PDF
导出
摘要 随着网络的增大,过去深圳10kV配网中性点不接地运行,变电设备事故频繁。10kV网络中性点经16Ω电阻接地后,变电站10kV单相接地避免发展成变压器出口的三相短路,配网过电压水平大大降低,10kV设备,特别是变压器运行的可靠性大大提高。 In the past, neutral operated in non-grounding manner in 10kV power distribution system, with the increasing of the system, the power equipment failure happened frequently. After neutral is grounded through 16Ω resistance, the growth of 10kV single-phase grounding failure in substation is avoid, the three-phase short-circut failure of transformer output and the system overvoltage level are greatly decreased, 10kV equipment, especially transformer's operation reliability is greatly increased.
机构地区 深圳供电局
出处 《高电压技术》 EI CAS CSCD 北大核心 1997年第3期78-80,共3页 High Voltage Engineering
关键词 深圳市 配电网 中性点 电阻接地 可靠性 power distribution system resistance grounding reliability